UPS5000-A-(600 kVA-800 kVA)
User Manual (40 kVA)
Before performing a shallow discharge test, ensure that:
Automatic Shallow Discharge Test
Step 1 On the home screen of the LCD, choose System Info > Settings > Battery Param. and set
Sched. shallow dis. test to Enable.
Step 2 Set Sched. shallow dis. test time and Sched. shallow dis. test interval as required. After
setting is complete, the system will perform automatic shallow discharge tests based on the
settings.
----End
Manual Shallow Discharge Test
Step 1 On the home screen of the LCD, choose System Info and tap
Maintenance screen.
Step 2 On the Maintenance screen, tap Battery Maint, as shown in
Step 3 Tap Start next to Shallow Dis. Test to start a shallow discharge test.
Figure 5-24 Starting a shallow discharge test
Issue 03 (2017-10-16)
The UPS works in normal mode with a load ratio fluctuation less than 10%.
The UPS generates no battery overtemperature, overvoltage, or overcurrent alarm. No
generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is generated.
When the battery test is complete, the test data is used as common test data. Record the data obtained
from the latest five tests.
The shallow discharge test automatically stops in any of the following cases:
The battery discharge capacity reaches the specified value (10%–50%, 20% by default).
The discharge voltage reaches the warning threshold (calculated in real time).