Danfoss VLT FC Series Operating Instructions Manual page 49

Option panel
Hide thumbs Also See for VLT FC Series:
Table of Contents

Advertisement

Electronically Controlled B...
Input Conn.
Term.
1
2
3
4
5
6
X57
7
8
9
10
Output Conn.
Term.
1
2
3
4
X59
5
6
7
8
Relay Output
Term.
1
X56
2
3-12
Table 6.5 ECB Card Terminals
Option Panel Operating Instructions
Function
Digital input for safety stop
Common
Factory use only
No function
Factory use only
Factory use only
Factory use only
Digital input for remote bypass enable
Digital input overrides system to Bypass Mode ignoring all
other inputs and commands, except for safety stop on
terminal 1.
Digital input for remote overload reset
Function
Common for binary I/O
Common for binary I/O
No function
No function
Digital output indicates panel is in Drive Mode.
Digital output indicates panel is in Bypass Mode
Common for binary I/O
Common for binary I/O
Function
N.O. contact for running in bypass or drive
N.O. contact for running in bypass or drive
Factory use only
®
MG14I102 - VLT
is a registered Danfoss trademark
Type
User supplied dry contact
User supplied dry contact
User supplied dry contact
User supplied dry contact
User supplied dry contact
24 V DC digital output
24 V DC digital output
Relay output for user
Relay output for user
6
6
47