Installation
Illustration 3.3 Proper Lifting Method

3.2.3 Forklift

Only a competent lift operator with additional
support personnel should attempt moving the
unit.
Carefully position forklift and ensure stability
before lift.

3.2.4 Shipping Weights

NOTE
WEIGHTS LISTED IN Table 3.1 ARE APPROXIMATE FOR BASE
UNITS. OPTIONS CAN ADD OR REDUCE WEIGHT OF UNIT.
Frame
Tier 1 [lbs]
A2-A3
30
A5
35
B1
65
B2
70
C1
100
C2
130
D1
220
D2
407
Table 3.1 Approximate Shipping Weights
Option Panel Operating Instructions
28 in. min
Tier 2 [lbs]
Tier 3 [lbs]
35
55
55
80
85
110
105
180
145
215
190
285
420
585
662
1037
®
MG14I102 - VLT
is a registered Danfoss trademark

3.2.5 Cooling

Mount the drive and panel vertically.
Option panels rely on the ambient air for cooling,
it is important to observe the limitations on
ambient air temperature. See Table 3.2 for
temperature rating data. Derating concerns start
above 3300 feet elevation above sea level.
Most option panels with drives may be mounted
side-by-side without additional side clearance. A2
and A3 units require 1.5 in. clearance between
units (see Illustration 3.4).
Top and bottom clearance is required for cooling
(see Illustration 3.5). Generally, 100 to 250 mm (4
to 10 inches) minimum clearance is required,
depending upon the hp (kW) of the unit. See the
mechanical drawing shipped with the unit for
specific requirements.
No additional back plate is required for drives
with the option panel.
Units may be mounted flush to the wall or free
standing. A free-standing mounting kit is
available from Danfoss.
See Table 3.2 for temperature ratings.
Frame Size
NEMA 1
45 °C
A2-A3
A5
NA
45 °C
B1-C1
40 °C
C2, D1-D2
Table 3.2 Temperature Ratings
Illustration 3.4 Side Cooling Clearance, A-2 and A-3 Frames
NEMA 12
NA
40 °C
40 °C
40 °C
1.5 in min.