Installation
Type Code Char
Type Code
[HP]
0.50
3
3
0.75
1
1.5
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
350
400
Table 3.14 600 V Max Wire - Input
24
Option Panel Operating Instructions
Disc. W/O Mains Fusing
CHAR 15&16
MD,ND
Maximum Wire Size [AWG]
Maximum Wire Size [AWG]
8
8
8
8
8
8
8
8
8
8
8
8
8
3
1/0
1/0
1/0
300KCM
300KCM
250 KCM
250 KCM (DUAL)
250 KCM (DUAL)
250 KCM (DUAL)
250 KCM (DUAL)
350 KCM (DUAL)
MG14I102 - VLT
Disc. W Mains Fusing
Disc. W 100KIA SCCR
CHAR 15&16
MM,NM
Maximum Wire Size [AWG]
4
4
4
4
4
4
4
4
4
4
4
4
4
4
1/0
1/0
1/0
1/0
300KCM
250 KCM
250 KCM (DUAL)
250 KCM (DUAL)
250 KCM (DUAL)
250 KCM (DUAL)
250 KCM (DUAL)
250 KCM (DUAL)
250 KCM (DUAL)
250 KCM (DUAL)
350 KCM (DUAL)
350 KCM (DUAL)
®
is a registered Danfoss trademark
Circuit Breaker
CHAR 15&16
CHAR 15&16
MN,NN
Maximum Wire Size [AWG]
8
8
8
8
8
8
8
8
8
8
4
4
4
4
1/0
1/0
1/0
1/0
300KCM
250 KCM
2/0 (DUAL)
2/0 (DUAL)
250 KCM (DUAL)
250 KCM (DUAL)
250 KCM (DUAL)
250 KCM (DUAL)
CD,FD
10
10
10
10
10
10
10
10
10
3
3
3
2
2
1/0
1/0
300KCM
300KCM
300KCM
Need help?
Do you have a question about the VLT FC Series and is the answer not in the manual?
Questions and answers