Danfoss VLT FC Series Operating Instructions Manual page 34

Option panel
Hide thumbs Also See for VLT FC Series:
Table of Contents

Advertisement

Start Up
within 3%. If incorrect, see 8 Start Up Troubleshooting for
isolation procedures.
10.
Check full load amps in bypass mode on motor
terminals.
a. Put unit into bypass mode.
b. Check full load amps on terminals T1, T2, and T3. Verify
4
4
motor amps are within motor FLA rated current and
balanced within 3%. If incorrect, see 8 Start Up Trouble-
shooting for isolation procedures.
For steps 11-13, see 5 Electromechanical Bypass (EMB)
Operation and 6 Electronically Controlled Bypass (ECB)
Operation for details.
11.
Check operation of any optional functions to
confirm they work, as applicable. Options may
include run permissive, fire mode, common start/
stop, or others.
12.
Exercise safety circuit and verify that unit stops
running.
13.
Exercise start/stop circuit and verify that unit
starts and stops with system in auto mode of
operation.
32
Option Panel Operating Instructions
®
MG14I102 - VLT
is a registered Danfoss trademark

Advertisement

Table of Contents
loading

Table of Contents