[Parameter setup example]
Link the CIDRW controller to the upstream controller, and boot up the terminal software. Then,
power UP the CIDRW controller in setup mode.CIDRW
SETUP_START <L21 ><XXX.XX,YYY.YY>
_
For a parameter being altered, execute parameter definition.
SETUP_START <L21 ><XXX.XX,YYY.YY>
S_BAUD=19200 [ENTER]
S_DEVID=1 [ENTER]
S_BNO=0 [ENTER]
_
Once a first parameter is defined, the ALARMS status indicator flashes.
Execute parameter change process. The entered parameter is checked and written into the CIDRW
controller.
SETUP_START <L21 ><XXX.XX,YYY.YY>
S_BAUD=19200
S_DEVID=1
S_BNO=0
::END [ENTER]
Once setup process is complete, a message indicating the result appears.
SETUP_START <L21 ><XXX.XX,YYY.YY>
S_BAUD=19200
S_DEVID=1
S_BNO=0
::END
SETUP_COMPLETE
_
The ALARMS status indicator stably lights.
Once the whole setup procedure is successfully complete, restart the CIDRW controller in normal
operating mode.
It will be convenient to create a text file such as a one shown below and transmit the file using the text
file send function of the terminal (upstream controller).
#Parameter Setting File for SystemA
#Protocol
S_BAUD=19200
S_DEVID=1
#SECS
S_BNO=0
::END
Prm.txt
Section 5
Setup Mode
* [ENTER] does not appear on
the screen.
* [ENTER] does not appear on
the screen.
V700-L21
User's Manual
65