A.2 DCT2000 Series
Electromagnetic Compatibility: UL, UL2808.
Model
Number
DCT-S201B
DCT-S211B
_A
DCT-S221B
DCT-S231B
DCT-S241B
DCT-S251B
DCT-S261B
DCT-S2C1B
DCT-S271B
*1: See the following table for detailed information on the external dimensions and sizes of opening.
A - 4
External Dimension:
186.5 x 52 x 252
Size of Opening:
81 x 160.5
Measurem
Primary
Secondary
ent
Current
Current
Accuracy
1.0%
100 A
0.5%
200 A
0.5%
300 A
0.5%
400 A
0.5%
500 A
0.5%
600 A
0.5%
750 A
0.5%
800 A
0.5%
1000 A
External
Rated Burden
Dimension*1
(VA)
5 A
1
5 A
1
90 x 40 x 110
5 A
1.5
5 A
1.5
5 A
2.5
5 A
2.5
115 x 57 x 158
5 A
2.5
5 A
3.75
5 A
5
Size of Opening*1
(mm)
(mm)
20 x 30
50 x 80

Advertisement