Delta DPM-C501L Operating Manual page 60

Di/do type power meter
Hide thumbs Also See for DPM-C501L:
Table of Contents

Advertisement

DP M- C5 0 1L O pe r a t io n M a nu a l
41419 Setting of digital input #3
58A
41420 Setting of digital input #4
58B
41421 Setting of relay output #1
58C
_5
41422 Setting of relay output #2
58D
41425 Status of digital input #1
590
5 - 2 8
1: Enable
0: Disable
1: Enable
0: Disable
1: Enable
Alarms:
0: Disable
1: Over current
2: Over line voltage
3: Under line voltage
4: Over phase voltage
5: Under phase voltage
6: Over active energy
7: Over reactive energy
8: Over apparent power
9: Over frequency
10: Under frequency
11: Digital input #1
12: Digital input #2
13: Digital input #3
14: Digital input #4
15: Communication
(when set for Relay Output
#1, register 0x594 is writable)
(when set for Relay Output
#2, register 0x595 is writable)
0: Low
word
2
R/W
word
2
R/W
word
2
R/W
word
2
R/W
word
2
R