4.2.5

Set up the Potential Transformer (PT)

Voltage for the primary-side potential transformer; 1– 65535 V, 1 V is default.
Voltage for the secondary-side potential transformer; 1–9999 V, 1 V is default.
Steps
1.
Press NEXT until the first digit starts blinking
2.
Use UP and DOWN to select the number for the primary-side potential transformer.
3.
Press NEXT to confirm the setting and then set the next number for the primary-side potential
transformer.
4.
Repeat steps 2–3 to complete setting the 5-digit number for the primary-side potential transformer.
Press NEXT to set the secondary-side potential transformer.
5.
When the option starts blinking, use UP and DOWN to select the number of the secondary-side
potential transformer.
6.
Press NEXT to confirm the setting and then set the next number for the primary-side potential
transformer.
7.
Repeat steps 5–6 to complete setting the 4-digit number for the primary-side potential transformer.
8.
Press NEXT to save the setting.
Note: You can go back to the previous setting item by pressing BACK anytime, whether you have completed or
canceled the setting.
4.2.6

Set up Reset (RST)

No action (nonE): Do not reset.
Restore to defaults (dEF): Restore the power meter parameters to the default settings.
Reset the accumulated value of electric energy (PH) on the meter to zero.
Clear all detected alarm (ALA) logs on the meter.
Steps
1.
Press NEXT until the option starts blinking.
2.
Use UP and DOWN to select the reset options.
3.
Press NEXT to save the setting.
Note: You can go back to the previous setting item by pressing BACK anytime, whether you have completed or
canceled the setting.
4.2.7

Digital Input (DI)

Digital input #1 (D1): Enable (on) or disable (oFF) the first digital input, default: disable (oFF)
Digital input #2 (D2): Enable (on) or disable (oFF) the second digital input, default: disable (oFF)
Digital input #3 (D3): Enable (on) or disable (oFF) the third digital input, default: disable (oFF)
Digital input #4 (D4): Enable (on) or disable (oFF) the fourth digital input, default: disable (oFF)
Steps