1.3

RJ71GP21(S)-SX

This section describes the names of each part of the RJ71GP21(S)-SX.
(1)
(2)
(3)
(4)
(6)
No.
Name
(1)
RUN LED
*1
ERR LED
*1
PRM LED
*1
D LINK LED
SD/RD LED
*1
L ERR LED
EXT PW LED
(2)
Dot matrix LED
(3)
Optical connector (IN
connector)
(4)
Optical connector (OUT
connector)
(5)
External power supply terminal
block
(6)
Production information marking
1 PART NAMES
26
1.3 RJ71GP21(S)-SX
(5)
Description
Indicates the operating status.
On: Normal operation
Off: Error ( MELSEC iQ-R CC-Link IE Controller Network User's Manual (Application))
Indicates the error status of the module.
On, flashing: Error ( MELSEC iQ-R CC-Link IE Controller Network User's Manual (Application))
Off: Normal operation
Indicates the operating status.
On: Operating as a control station
Off: Operating as a normal station
Indicates the data link status.
On: Data link (cyclic transmission being performed)
Flashing: Data link (cyclic transmission stopped)
Off: Data link not performed (disconnection)
Indicates the data sending/receiving status.
On: Data being sent or received
Off: Data not sent nor received
Indicates the line error status.
On: The following errors has occurred in the line connected to the own station port.
• A receive data is faulty (receive frame error).
• Loopback is performed in the own station.
• Cable disconnection
• Cable insertion error
Off: The module or line is in the following status.
• A received data is normal (receive frame normal)
• Loopback is not performed in the own station.
Indicates the external power supply status.
On: The external power being supplied
Off: The external power not supplied
Displays the station number set in the module and the module communication test result.
Station number not set: "  "
Control station, normal station: 1 to 120
In offline mode: ""
For display of the module communication test result, refer to the following.
( MELSEC iQ-R CC-Link IE Controller Network User's Manual (Application))
A connector to connect the optical fiber cable. Connect to OUT connector of another station.
A connector to connect the optical fiber cable. Connect to IN connector of another station.
A terminal block to connect a wire for the external power supply to the RJ71GP21S-SX.
Shows the production information (16 digits) of the module.
(1)
(2)
(3)
(4)
(6)
*2