9.3.2 Outdoor Temperature Compensation

Airflow
Outdoor temperature compensation of the airflow can be
activated if it is desired to reduce the airflow in the winter-
time.
In the flow regulation mode, the current airflow is redu-
ced. In the pressure regulation mode, the current setpoint
for pressure is reduced.
The function has no effect if the airflow is demand-con-
trolled.
The airflow is reduced as a percentage of the current
airflow/pressure.
Settings:
Value
Y1, max permissible reduction
X1, breakpoint
X2, breakpoint
We reserve the right to alter specifications without notice.
Setting
Factory
range
setting
0-50%
30 %
-30 – -10 °C
-20 °C
-10 – +15 °C
+10 °C
INSTALLATION
FUNCTIONS
*FUNCTIONS*
TEMPERATURE
AIR FLOW/PRESSURE
FILTER
OPERATION
HEATING
COOLING
HUMIDITY
IN/OUTPUTS
IQnomic Plus
ALL YEAR COMFORT
OPTIMIZE
0%
-10%
-20%
Y1
-30%
X1
-40%
-50%
-30
-20
-10
X = Outdoor air temperature °C
Outdoor air compensation according to factory settings
involves:
Outdoor temperature +10 °C (Breakpoint X2): Compensa-
tion starts and gradually proceeds between 0–30 % down
to outdoor air temperature -20 °C.
Outdoor air temperature -20 °C (Breakpoint X1): Constant
compensation proceeds at 30 % (max reduction Y1).
GB.GOLDLP.170830
* AIRFLOW/PRESSURE *
SA FAN REGULATION
EA FAN REGULATION
CLEAN AIR CONTROL
OUTDOOR TEMP COMP.
SA DOWN REGULATION
SLAVE CONTROL
X2
0
+10
+20
www.swegon.com