Function
90
No comm. with press. sensor by EA prefilter
91
Frost prot. for preheating, below alarm limit
92
Frost prot. for preheating sensor, faulty
93
Preheating sensor faulty
94
Electric air heater for preheating, tripped
95
Preheating below setpoint
96
Lost settings
99
Time lock tripped
102
Cooling valve I/O-7 defective
103
Heating valve I/O-7 defective
104
Cool. circuit pump I/O-7 tripped
105
Heat. circuit pump I/O-7 tripped
106
Cooling water temp. I/O-7 below set point
107
Heat. water temp. l I/O-7 below set point
108
Cooling water temp. I/O-7 above set point
109
Heating water temp. I/O-7 above set point
110
Cooling water temp. sensor I/0-7 defective
111
Heating water temp. sensor I/0-7 defective
143
No communication - OPTIMIZE
160
No communication VOC sensor
161
Internal comm. error VOC sensor
162
Internal error VOC sensor
163
VOC level below/over alarm limit
* Not adjustable, always stops the air handling unit
** Not adjustable, stops the air handling unit at temperature below +5 °C
*** Blocked if the hand terminal does not display the main menu.
**** Cannot be blocked.
Adjustments carried out by:
Date
Company
Name

We reserve the right to alter specifications without notice.

Factory preset value
Priority
Indication
0=blocked
LED
A=A alarm
0=Off
B=B alarm
1=On
B***
1
A
1
A
1
A
1
A***
1
A***
1
A
1
A
1
B***
1
A***
1
B***
1
A***
1
B***
1
A***
1
0***
1
0***
1
B
1
A
1
B***
1
B
1
B
1
B
1
B
1
Adjusted value
Effect
Priority
Indication
0=Operat. 0=blockedt
1=Stop
A=A alarm
B=B alarm
0
1
1
1
1
1
1
1
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
GB.GOLDLP.170830