USER LEVEL

7.1 Temperature

The basic functions can be preset at INSTALLATION LE-
VEL and the values can be read and set at USER LEVEL.
See also Section 9.2 in which the functions for
temperature are described in detail.
IMPORTANT! If you intend to substantially alter the tempera-
ture settings, you should first stop the air handling unit before
doing so.

7.1.1 Readings

Used for checking the performance.

7.1.2 Settings

ERS REGULATION 1
The control unit regulates the relationship between the supply
air and the extract air temperatures according to a factory
preset curve.
Settings (see the chart to the right as well):
Value
Step
EA/SA Differential
Breakpoint (refers to
extract air temperature)
ERS REGULATION 2
The control unit regulates the relationship between the supply
air and extract air temperatures according to a custom-plotted
curve. The curve has three adjustable breakpoints.
Settings (see the chart to the right as well):
Value
Extract air temperature
X1
X2
X3
Supply air temperature
Y1
Y2
Y3
SUPPLY AIR REG.
Settings:
Value
Supply air temperature
setpoint
EXTRACT AIR REG.
Settings:
Value
Extract air/room temp.
Setpoint
Min. supply air temperature
Max. supply air temperature
*) The setting range can be changed. See 14.3, Min/Max
Adjustment.
12
www.swegon.com
Setting
Factory
range
settings
1 - 4
1
1-5 °C*
2 °C
15-23 °C*
20 °C
Setting
Factory
range
settings
10-40 °C
15 °C
10-40 °C
20 °C
10-40 °C
22 °C
10-40 °C
20 °C
10-40 °C
18 °C
10-40 °C
14 °C
Setting
Factory
range
settings
15-40 °C*
21.5 °C
Setting
Factory
range
settings
15-40 °C*
21.5 °C
13-25 °C*
15 °C
18-45 °C*
28 °C
TEMPERATURE
*TEMPERATURE*
READINGS
SETTINGS
*TEMPERATURE*
READINGS
SETTINGS
ERS REGULATION 1
ERS REGULATION 2
ERS Regulation 1
20
15
10
15
Extract air temperature °C
ERS Regulation 2
22
1
20
15
10
9
12
15
X = Extract air temperature °C
We reserve the right to alter specifications without notice.
GB.GOLDLP.170830
Important! The
appearance of the
menus varies depending
on the type of air
handling unit and
functions selected.
SUPPLY AIR REG.
EXTRACT AIR REG.
Step 2
Breakpoint
Step 3
Step 4
20
2
3
20
25
25
27