We Reserve The Right To Alter Specifications Without Notice - Swegon GOLD LP Operation And Maintenance Instructions

Applicable to program version 3.04 and newer versions
Hide thumbs Also See for GOLD LP:
Table of Contents

Advertisement

Alarm text
Function
39
EL.HEATING COIL TRIPPED
The thermal overload protection has tripped or is not
connected.
40
EXTRACT AIR TEMP BELOW ALARM LIMIT
The extract air temperature is below preset alarm
limit for more than 20 minutes.
41
SUPPLY AIR TEMP BELOW SETPOINT
The supply air temperature is below the preset set-
point (for ERS and Supply air regulation) or Min
SA temp (for Extract air regulation) longer than 20
minutes.
42
EXT. ALARM No.1 TRIPPED
External alarm, connected to control unit input Inp. 1
or Inp. 2, has tripped.
43
EXT. ALARM No.2 TRIPPED
External alarm, connected to control unit input Inp. 1
or Inp. 2, has tripped.
44
SA DUCT PRESSURE BELOW SETPOINT
EA DUCT PRESSURE BELOW SETPOINT
45
Pressure in supply/extract air duct, if pressure trans-
ducers are connected, has been more than 10%
below its setpoint for more than 20 minutes.
46
SA DUCT PRESSURE ABOVE SETPOINT
EA DUCT PRESSURE ABOVE SETPOINT
47
Pressure in supply/extract air duct, if pressure trans-
ducers are connected, has been more than 10%
above its setpoint for more than 20 minutes.
48
SUPPLY AIRFLOW BELOW SETPOINT
EXTRACT AIRFLOW BELOW SETPOINT
49
The supply/extract airflow has been more than 10%
below its setpoint for more than 20 minutes.
50
SUPPLY AIRFLOW ABOVE SETPOINT
EXTRACT AIRFLOW ABOVE SETPOINT
51
The supply/extract airflow has been more than 10%
above its setpoint for more than 20 minutes.
52
SUPPLY AIR FILTER DIRTY
EXTRACT AIR FILTER DIRTY
53
The pressure across the supply /extract air filters has
exceeded the preset alarm limit for more than 10
minutes.
54
SERVICE PERIOD PAST ALARM LIMIT
The preset service period has expired.
If the alarm is RESET via the hand-held micro termi-
nal, the alarm will be initiated again after 7 days.
A new service period can be set in the ALARM SET-
TINGS menu.
*** Blocked if the hand terminal does not display the main menu.
48
www.swegon.com
Priority
Stop
0=blocked
0=In operat.
A=A alarm
1=Stop
B=B alarm
A ***
1
A ***
1
A ***
1
A ***
1
B ***
0
B ***
0
B ***
0
B ***
0
B ***
0
B ***
0
B ***
0
B ***
0
B ***
0
B ***
0
B ***
0
B ***
0

We reserve the right to alter specifications without notice.

GB.GOLDLP.170830
Indication
Delay
LED
0=Off
s=seconds
1=On
m=minutes
1
3 s
1
20 m
1
20 m
1
Set time
1
Set time
1
20 m
1
20 m
1
20 m
1
20 m
1
20 m
1
20 m
1
20 m
1
20 m
1
10 m
1
10 m
1
Set time
Resetting
M=manual
A=automatic
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M