Advertisement

Alarm text
Function
107
HEATING WATER TEMP I/O-7 BELOW SET POINT.
Temperature for heating water control on I/O module
is continuously 7°C below its current set point.
108
COOLING WATER TEMP I/O-7 ABOVE SET POINT
Temperature for cooling water control on I/O module
is continuously 7°C above its current set point.
109
HEATING WATER TEMP I/O-7 ABOVE SET POINT
Temperature for heating water control on I/O module
is continuously 7°C above its current set point.
110
COOLING WATER TEMP SENSOR I/O-7 DEFECTIVE
Obtained if the cooling water temperature sensor
temp is not connected or is defective.
111
HEATING WATER TEMP SENSOR I/O-7 DEFECTIVE
Obtained if the heating water temperature sensor is
not connected or is defective.
143
NO COMMUNICATION W OPTIMIZE
The AHU control unit cannot establish correct com-
munication with OPTIMIZE.
160
NO COMMUNICATION VOC SENSOR
The air handling unit's control unit cannot establish
correct communication with the VOC sensor.
161
INTERNAL COMM.-ERRO VOC SENSOR
The air handling unit's control unit cannot establish
correct communication with the VOC sensor.
162
INTERNAL ERROR VOC SENSOR
VOC sensor defective.
163
VOC LEVEL BELOW/ABOVE ALARM LIMIT
The VOC sensor has read a level below or above the
set point alarm limit for more than 60 seconds.
*** Blocked if the hand terminal does not display the main menu.

We reserve the right to alter specifications without notice.

Priority
Stop
0=blocked
0=In operat.
A=A alarm
1=Stop
B=B alarm
A***
1
0***
1
0***
1
B
1
A
1
B***
0
B
0
B
0
B
0
B
0
GB.GOLDLP.170830
Indication
Delay
LED
0=Off
s=seconds
1=On
m=minutes
0
30 m
0
30 m
0
30 m
0
3 s
0
3 s
1
10 s
1
10 s
1
60 sec.
1
60 sec.
1
60 sec.
www.swegon.com
Resetting
M=manual
A=automatic
M
M
M
A
A
A
A
A
A
A
51