Morning Boost; Setpoint Temperature Displacement - Swegon GOLD LP Operation And Maintenance Instructions

Applicable to program version 3.04 and newer versions
Hide thumbs Also See for GOLD LP:
Table of Contents

Advertisement

9.2.5 Morning BOOST

The unit is utilised to heat the premises during a preset
period prior to the switch-in time set on the switch clock.
The function is used if the air recirculation section is instal-
led.
The unit starts early and uses the same operation and
temperature regulation settings as it would at the regular
start time.
If the extract air fan is not required to operate, the extract
airflow can be set to 0.
Damper output can be set to be inactive. This means that
connected dampers (e.g. outdoor air and exhaust air shut-
off dampers) are not affected. Normally these dampers
are closed when the unit is stopped and thus they remain
closed.
At the same time, the damper in the air recirculation sec-
tion, if included, will open.
Settings:
Value
Time for start prior to regular
start time according to switch clock
00:00
Damper output
Extract air fan
FL/Rum-temp
TL-min
TL-max
Settings:
Value
Setting range
External Extract air/Room Inactive//IQnomic
Communication
External Outdoor
Inactive//IQnomic
Communication
Alarms
0 - 9990 min.

9.2.6 Setpoint Temperature Displacement

Used for changing the supply air and extract air tempera-
ture setpoints by means of an external 0-10 VDC signal
(control unit terminals 35 (-), 37 (+)). The temperature can
be increased or decreased at certain times of the day by
means of an external switch clock or potentiometer, for
instance.
The setpoint can be influenced ±5 °C.
If the unit is operating in the supply air regulation mode,
the supply air temperature is displaced and if the unit is
operating in the extract air regulation mode, the extract
air temperature is displaced.
When the unit is operating in the ERS regulation 1 mode,
the difference between extract air and supply air is influ-
enced. The difference cannot be less than 0 °C. The diffe-
rence will decrease as the input signal increases.
If the unit is operating in the ERS regulation 2 mode, the
supply air setpoint will be offset.
When the function is activated, the setpoint is offset as
illustrated in the chart to the right.
We reserve the right to alter specifications without notice.
Setting
Factory
range
setting
hour, min.
Inactive
Inactive
Inactive
Inactive
10 - 30 °C
22 °C
8 - 20 °C
15 °C
16 - 50 °C
28 °C
Factory setting
Inactive
Inactive
5 min.
INSTALLATION
FUNCTIONS
*FUNCTIONS*
TEMPERATURE
AIR FLOW/PRESSURE
FILTER
OPERATION
HEATING
COOLING
HUMIDITY
IN/OUTPUTS
IQnomic Plus
ALL YEAR COMFORT
OPTIMIZE
INSTALLATION
FUNCTIONS
*FUNCTIONS*
TEMPERATURE
AIR FLOW/PRESSURE
FILTER
OPERATION
HEATING
HUMIDITY
COOLING
IN/OUTPUTS
IQnomic Plus
ALL YEAR COMFORT
OPTIMIZE
+5
+4
+3
+2
+1
0
-1
-2
-3
-4
-5
0
5
Control signal V DC
Setpoint temp displacement involves:
Control signal 0 V DC: The setpoint is lowered by 5 °C.
Control signal 5 V DC: Unchanged setpoint.
Control signal 10 V DC: The setpoint is increased by 5 °C.
Settings:
Value
Setpoint temp displacement
GB.GOLDLP.170830
* TEMPERATURE *
TEMPERATURE REG
OUTDOOR TEMP COMP
SUMMER NIGHT COOL
INTERM. NIGHT HEAT
MORNING BOOST
SETPOINT TEMP DISPL
EXT. SENSORS
* TEMPERATURE *
TEMPERATURE REG
OUTDOOR TEMP COMP
SUMMER NIGHT COOL
INTERM. NIGHT HEAT
MORNING BOOST
SETPOINT TEMP DISPL
EXT. SENSORS
10
Setting
Factory
range
setting
Inactive/active Inactive
www.swegon.com
23