Measure voltage at J4 between: pin-1 (GND) and pin-3 (SWVBAT) using a MM set to volts DC. Voltage should be
greater than 11.9Vdc. If voltage is equal to or less than 11.9, return to test sequence outlined in the Power
Troubleshooting flowchart (Figure 97:).
Measure voltage at J4 between: pin-1 (GND) and pin-2 (VBAT) using a MM set to volts DC. Voltage should be greater
than 11.9Vdc for this unit. If voltage is equal to or less than 11.9, return to test sequence outlined in the Power
Troubleshooting Flowchart (Figure 97:).
7.4.4 Transceiver Check
To perform a transceiver check:
If available, use a wattmeter to check transceiver output power. Refer to manufacturer's documentation for measuring
instructions.
If available, use two hand-held transceivers, and verify communication path between master and remote sites. Voice-
activated interface can be used, if available.
Verify that transceiver is set to the correct frequency. Refer to manufacturer's documentation for checking frequency
instructions.
If a directional antenna is used, verify the orientation to the antenna to the master site.
J12
XA2
Figure 103: XFC
157
J11
A
B
1
9
2
J4
10
CD
3
11
4
TXD/BUS+
12
5
RXD/BUS-
13
6
14
7
CTS
15
8
OPER
16
XA1
G4
Communication Wiring
XFC G4 2103335 Rev AB
B
A
CTS
GND
DTR
VBATT
SWVBATT
TXD/BUS+
BUS+
RTS
RXD/BUS-
BUS-
RTS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents