ABB i-bus KNX
2

Device technology

2.1

ES/S 4.1.2.1

2.2

Technical data

Supply
Outputs
Connections
Operating and display elements
Enclosure
Safety class
© 2010 ABB STOTZ-KONTAKT GmbH
Device technology
The Electronic Switch Actuator ES/S 4.1.2.1 is a modular installation device
in Pro M design. The device features four semiconductor outputs for control
of thermoelectric valve drives in heating and cooling systems. The outputs
can be operated with either DC or AC voltage (24...230 V AC/DC).
Each output is short-circuit and overload protected. The outputs can be
directly controlled using the manual pushbuttons. The LEDs on the front
of the device signal the status of the outputs.
Bus voltage
Current consumption, bus
Leakage loss, bus
Leakage loss per device at max. load
4 semiconductor outputs
Rated voltage U
n
Rated current I
per output
n
Inrush current per output
Number of thermoelectric valve drives per
output
KNX
4 x outputs A...D,
2 x supply U
for 2 outputs each
n
Button/LED Programming
Button Manual operation
and
LED Manual operation
Button ON/OFF
and LED Status
output
Button Reset
and LED Fault
IP 20
II
21...32 V DC
< 12 mA
Maximum 250 mW
Maximum 4 W
Non-isolated, short-circuit proofed
24...230 V AC/DC +/-10%, 50/60 Hz
Separate supply of the outputs is possible
Example: A+B 230 V AC, C+D 24 V DC
1 A resistive load at T
8 A for max. 1 second at T
The number of connectible valve drives per
output is dependent on the maximum inrush
current (8 A) or continuous current (1 A) of
the output. They may not be exceeded when
several valve drives are connected in parallel.
Observe the technical data for the valve drive.
Via bus connection terminals
Using universal head screw terminals
2
0.2... 4 mm
finely stranded, 2 x 0.2...2.5
2
2
mm
, 0.2... 6 mm
single core, 2 x 0.2...4
2
mm
For assignment of the physical address
To switch to manual mode
per
For control of the output and display of the
status
per output
For reset and indication of a fault
To EN 60 529
To EN 61 140
up to 45 °C
amb
20 °C
amb
5