Device Technology; Aa/S 4.1.2 Analogue Actuator, 4-Fold, Mdrc; Technical Data - ABB i-bus KNX AA/A 2.1.2 Product Manual

Analogue actuator
Table of Contents

Advertisement

®
ABB i-bus
KNX

Device technology

2
Device technology
2.1

AA/S 4.1.2 Analogue Actuator, 4-fold, MDRC

Analogue Actuator AA/S 4.1.2
2.1.1

Technical data

Supply
Analog outputs
Output current
Operating and display elements
Connections
Degree of protection
Protection class
Isolation category
KNX safety voltage
The Analogue Actuator converts
telegrams received via KNX into analog
output signals. The device has four
outputs. The analog outputs can be used
independently of one another as current
or voltage outputs with adjustable output
signals.
Auxiliary voltage
Power supply
KNX current consumption
KNX power loss
Power loss P
4, A...D
Voltage signals
Current signal
Output signal load
Dielectric strength
Voltage signal
For 1...10 V output and ballasts
Current signal
Programming button/LED (red)
A...D status LED (yellow)
KNX status LED (green)
Power LED (green)
KNX connection
Analog outputs A...D
Tightening torque
IP 20
II
Overvoltage category
Pollution degree
SELV 24 V DC
The Analogue Actuator is a modular
installation device for installation in the
distribution board. It connects to the
KNX via a bus connection terminal.
The device requires an external
100...240 V AC auxiliary voltage.
The device is parameterized and
programmed using ETS.
100...240 V AC +10 %/-15 %, 50/60 Hz
Via ABB i-bus KNX
Max. 12 mA
Max. 250 mW
0.8 W
0...1 V DC
0...5 V DC
0...10 V DC
1...10 V DC
0...20 mA DC
4...20 mA DC
Depending on parameterization
≥ 1 kohm
Voltage signal:
≤ 500 ohms
Current signal:
24 V AC
34 V DC
Max. 10 mA per channel
Max. 1 mA per channel
Max. 20 mA per channel
For assignment of the physical address
Channel A...D status display
KNX status display
Auxiliary voltage display
Bus connection terminal, screwless
Screw terminals
0.2...4.0 mm
2
rigid/flexible
with/without ferrules
0.2...4.0 mm
2
solid-core
Max. 0.6 Nm
To DIN EN 60 529
To DIN EN 61 140
III to DIN EN 60 664-1
II to DIN EN 60 664-1
AA/S 4.1.2, AA/A 2.1.2 | 2CDC505163D0201 7