Parameter Window A: Functions - ABB ES/S 4.1.2.1 User's Product Manual

I-bus knx electronic switch actuator
Table of Contents

Advertisement

ABB i-bus KNX
3.2.4
Parameter window
A: Functions
© 2010 ABB STOTZ-KONTAKT GmbH
Commissioning
In parameter window A: Functions, various functions for each output can
be activated.
Enable communication object
"Block" 1 bit
Options:
no
yes
yes: The 1 bit communication object Block, page 46, is enabled.
An additional parameter is displayed:
Block on object value
Options:
1
0
Here you set the value of the communication object used to block
the output.
Enable communication object
"Forced operation" 1 bit
Options:
no
yes
yes: The 1 bit communication object
abled. Using forced operation, the operation of the output is inhibited
and the output assumes a defined state.
With option yes, the following parameters become visible:
Forced operation on object value
Options:
1
0
Here you set the value of the communication object used to forcibly
operate the output.
Forced
operation, page 46, is en-
32

Hide quick links:

Advertisement

Table of Contents
loading