4 Installation
I
AHF,N
[Amp]
10
19
26
35
43
72
101
144
180
217
289
324
4
Table 4.9: AHF005 and AHF010, 500-525V, 50Hz
I
AHF,N
[Amp]
43
72
101
144
180
217
289
324
370
Table 4.10: AHF005 and AHF010, 690V, 50Hz
NB!
See the section on fuses in the

4.1.6 Over Temperature Switch

The Danfoss harmonic filters AHF 005 and AHF 010 are equipped with a galvanic isolated thermal switch (not PELV), that is closed under normal
operating conditions and open if the filter is overheated.
When connecting the A/B terminals directly to terminal 12 and 27 of the drive, Protective Extra Low Voltage (PELV) can no longer
be guaranteed!
NB!
A controlled ramp down within 30 s is allowed without causing overheat damage to the filter.
22
Ordering Number
AHF 005
175G6644
175G6645
175G6646
175G6647
175G6648
175G6649
175G6650
175G6651
175G6652
175G6653
175G6654
175G6655
Ordering Number
AHF 005
130B2328
130B2330
130B2331
130B2333
130B2334
130B2335
Design Guide
.
Example: Connect terminal A of the harmonic filter to terminal 12 or13
(voltage supply digital input, 24V) of the Danfoss frequency converter and
terminal B to terminal 27 (digital input "Coast Inverse") the frequency
converter will let go of the motor (coasting) and thereby unload the filter
if an over temperature is detected.
®
MG.80.C2.02 - VLT
is a registered Danfoss trademark
AHF 005/010 Operating Instructions
Ordering Number
AHF 010
175G6656
175G6657
175G6658
175G6659
175G6660
175G6661
175G6662
175G6663
175G6664
175G6665
175G6666
175G6667
Ordering Number
AHF 010
130B2293
130B2295
130B2296
130B2298
130B2299
130B2300
130B2301
130B2302
130B2304
Max Fuse Rating
[Amp]
16
35
50
50
63
125
160
250
315
315
500
500
Max Fuse Rating
[Amp]
63
125
160
250
315
315
500
500
630