2 Ordering Numbers
⋆ Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on 500V and assuming typical motor
load. FC 300 is based on an 160% torque application, while FC 100 and FC 200 series are based on 110% torque application.
The pre-calculated filter current may be varying from the input current ratings of FC 100, FC 200 and FC 300 series as stated in the respective
operating instructions, as these numbers are based on different operating conditions.
2
2.1.6 Ordering Numbers, 690V, 50Hz
Danfoss Frequency Converter Series *
AQUA, HVAC,
Automation HO
P37K-P45K
P55-P75K
P90K-P110
P132
P160
P200
P250
P315
Table 2.6: AHF005 and AHF010, 690V, 50Hz
⋆ Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on 690V and assuming typical motor
load. FC 300 is based on an 160% torque application, while FC 100 and FC 200 series are based on 110% torque application.
The pre-calculated filter current may be varying from the input current ratings of FC 100, FC 200 and FC 300 series as stated in the respective
operating instructions, as these numbers are based on different operating conditions.
2.1.7 Calculation of the Exact Filter Size Needed
NB!
For optimal performance the harmonic filter should be sized for the mains input current to the frequency converter, i.e. the input current
drawn based on the expected load of the frequency converter and not the size of the frequency converter itself!
The mains input current to the frequency converter (I
φ)) of the motor. Both data are normally printed on the nameplate of the motor. In the case where the nominal motor voltage (U
actual mains-mains voltage (U
I FC
= 1.1 ×
I M
L
N
,
,
The harmonic filter chosen must have a nominal current (I
If several frequency converters are to be connected to the same filter, the harmonic filter must be sized according to the sum of the calculated mains
currents.
If the harmonic filter is sized for the load, and the motor of the corresponding frequency converter is changed, the current must be
re-calculated to avoid overload of the harmonic filter.
8
Automation NO
P37K
P45K-P55K
P75K-P90K
P110
P132
P160
P200
P250
) can by calculated using the nominal motor current (I
FC,L
) the calculated current must be corrected with the ratio between these voltages as shown in the equation below.
L
((
) / (
))
( ϕ ) ×
×
Cos
U M
U L
N
,
AHF,N
MG.80.C2.02 - VLT
Ordering Number
AHF 005
130B2328
130B2330
130B2331
130B2333
130B2334
130B2335
130B2331 + 130B2333
130B2333 + 130B2334
130B23314+ 130B2335
) equal to or larger than the calculated frequency converter mains input current (I
®
is a registered Danfoss trademark
AHF 005/010 Operating Instructions
I
AHF,N
AHF 010
[AMP]
130B2293
43 A
130B2295
72 A
130B2296
101 A
130B2298
144 A
130B2299
180 A
130B2300
217 A
130B2301
289 A
130B2302
324 A
130B2304
370 A
) and displacement power factor (Cos
M,N
) is unequal to the
M,N
).
FC,L