8-3. Address Switch Setting

SW1
Main/sub selection switch
OFF: System controller operates as main controller.
ON: System controller operates as sub-controller.
ALL/ZONE mode selection switch
ALL mode:
All indoor units can be controlled by system controller
ZONE 1, 2, 3, 4 mode:
Indoor units in one of zone 1, 2, 3, or 4 can be controlled
by system controller. All indoor units cannot be set.
ALL mode
ZONE 1 mode
ZONE 2 mode
ZONE 3 mode
ZONE 4 mode
Central control/Remote control mode selection switch.
OFF: Central control mode.
Individual setting by remote controller can be inhibited by
system controller.
ON: Remote control mode.
Setting by system controller is inhibited by other central
control equipment.
Central control Main/Sub selection switch
(OFF: Main, ON: Sub)
1
When AMY adaptor etc. is used with system controller,
set the switch to ON position.
2
When only one system controller is used, set the switch to
OFF position.
Except
, when multiple system controllers are used,
3
1
set only one system controller to OFF position and others to
ON position.
ALL mode system controller should be in OFF position.
(recommended)
(Central control) button operation switch
OFF:
(Central control) button operation is permitted.
ON :
button operation is inhibited.
*All switches are in OFF position at shipment.
Page 87
2
3
4
5
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
SW1
ON
1
2 3 4
OFF
87