11-4. Items to Check Before the Test Run

(1) Turn the breaker ON at least 12 hours in advance in order to energize the crank case heater.
(2) Fully open the closed valves on the liquid tube and gas tube sides.

11-5. Test Run Using the Remote Controller

(1) Press and hold the remote controller
G
"TEST" appears in the LCD display during the test run.
G
Temperature control is not possible when test run mode is engaged.
(This mode places a large load on the devices. Use it only when performing the test run.)
(2) Use either Heating or Cooling mode to perform the test run.
Note: The outdoor unit will not operate for approximately 3 minutes after the power is turned ON or after it stops
operating.
(3) If normal operation is not possible, a code appears on the remote controller LCD display.
Refer to the "Table of Self-Diagnostic Functions and Corrections" on the next page, and correct the problem.
(4) After the test run is completed, press the
display.
(This remote controller includes a function that cancels test run mode after 60 minutes have elapsed, in order to
prevent continuous test run operation.)
(5) For the test run of an inverter outdoor unit, operate the compressors for a minimum of 10 minutes.
* When performing a test run using a wired remote controller, operation is possible without attaching the
cassette-type ceiling panel.
("P09" will not be displayed.)

11-6. Precautions

G
Request that the customer be present when the test run is performed. At this time, explain the operation manual
and have the customer perform the actual steps.
G
Be sure to pass the manuals and warranty certificate to the customer.
G
Check that the AC 230 / 208 V power is not connected to the inter-unit control wiring connector terminal.
* If AC 230 / 208 V is accidentally applied, the indoor or outdoor unit control PCB fuse (0.5A for both indoor and
outdoor units) will blow in order to protect the PCB. Correct the wiring connections, then disconnect the 2P
connectors (indoor: blue, OC) (outdoor: blue, OC) that are connected to the PCB, and replace them with 2P
connectors (indoor: brown, EMG) (outdoor: brown, EMG). (Refer to the figure below.) If operation is still not
possible after changing the brown connectors, try cutting the varistor (VA002) (both indoor and outdoor).
(Be sure to turn the power OFF before performing this work.)
Indoor unit control PCB
IC8
Page 106
button for 4 seconds or longer. Then press the
button again. Check that "TEST" disappears from the LCD
VA002 (Varistor)
CN44 EMG
CN40 OC
Fuse (F3.05A)
Fig. 11-4
Outdoor unit control PCB
Varistor (black)
VA002
Fuse
0.5A
106
button.
Terminal plug (black)
EMG (brown) connector
OC (blue)
connector