Caution; Test Run Procedure - Sanyo C4272R S/C Installation Instructions Manual

Sanyo split system heat pump air conditioner installation instructions
Table of Contents

Advertisement

07-115 SSHP_II
5/7/07
4:00 PM
I X, T, U, K Type

11-2. Caution

G
This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor
unit.
G
The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The set-
tings required for operation were made at the time of shipment.
Only the correct combination of indoor and outdoor units can be used.
G
This test run manual describes primarily the procedure when using the wired remote controller.

11-3. Test Run Procedure

Recheck the items (see 11-4) to check before the test run.
Page 105
Check the combination (wiring) of indoor and
outdoor units.
Turn ON the indoor and outdoor power.
Automatic
address?
YES
Set the remote controller to "test run."
Has the
test run been
completed?
YES
Return the remote controller to normal
control.
(See 5-3)
NO
Check the warning code.
(See 10-5)
Refer to "Table of Self-Diagnostic
NO
Functions and Corrections" to
check the system.
Note: Check the indoor-side drainage.
Fig. 11-3
105