Service Menu - Brink Renovent Excellent 180 Installation Instructions Manual

Heat recovery appliance
Hide thumbs Also See for Renovent Excellent 180:
Table of Contents

Advertisement

6.5 Service menu

The service menu shows the most recent 10 fault messages.
In the event of a locking fault, the settings menu and the readout
menu are blocked and only the service menu can be opened;
Pressing the 'menu' key directly opens the service menu (only
for a locking fault).
The service menu can be called up as follows:
1. In operating mode, press the 'MENU' key. The display now
shows the settings menu.
2. Use the '+' and '-' keys to go to the service menu.
service menu
3. Activate the service menu.
Chapter 6
operating mode
settings menu
Fault code; Refer
to § 8.1 and § 8.2
for a fault code
explanation
No. fault message
Renovent Excellent 180
Display layout
4
Use the '+' and the '-' key to scroll through the readout
menu'.
- Display not any fault message.
- Current fault message (spanner on display).
- Unsolved fault message (no spanner on display).
5
Press the 'R' key twice to go to operating mode.
If no key is operated during 5 minutes, the appliance auto-
matically returns to operating mode.
operating mode
All fault messages can be deleted by pressing the "R" key in
the service menu during 5 seconds; This is only possible when
there is no active fault!
Rev. E
2x