Page 3
Children may not play with the appliance. If you need a new power cable, always order the replacement from Brink Climate Systems B.V. To prevent dangerous situations, a damaged mains connection must only...
These installation instructions describe both the standard Flair 400 and the Flair with Plus PCB. The Flair 400 is available in Left-hand and Right-hand versions; it is not possible to convert the left and right- hand models into one another.
*) Duct noise including end correction In practice the value may differ by 1dB(A) through measurement tolerances. Note: The stated value in the circle is the capacity (in Watt) per fan. Resistance of duct system [Pa] Flow rate [m Flair 400 614895-G Brink / 7...
All dimensions in millimeters. Diameter of all collars is 180 mm Supply air Exhaust air Extract Outdoor air Electrical connections Siphon connection Sealing cap unused condensate discharge connection; do not remove! Extract air filter Supply air filter Mounting bracket Flair 400 614895-G...
Page 9
All dimensions in millimeters. Diameter of all collars is 180 mm Supply air Exhaust air Extract Outdoor air Electrical connections Siphon connection Sealing cap unused condensate discharge connection; do not remove! Extract air filter Supply air filter Mounting bracket Flair 400 614895-G Brink / 9...
Power cable 230 volt Preheater Signal output (X19) ) Temperature sensor 24 volt connector (X18) Supply filter eBus connector (X17) Exhaust fan 24 volt connector (X16) Siphon Modbus/ internal bus connector (X15) Supply fan Multiple switch connector (X14) Flair 400 614895-G...
For external control a 4-way switch (® Connecting extra multiple switch with filter indication page 40) can, for example, be chosen, but control is also possible with the Brink Air Control (® Connecting Brink Air Control page 42), CO sensor(s) (®...
WiFi signal. 1 = For example a Flair 325 and a Flair 225 appliance with mounted Basic pcb 2 = Optional Plus pcb mounting plate 3 = Optional Plus pcb 4 = Optional Plus pcb cover Flair 400 614895-G...
5.2 Placing the appliance The Flair 400 appliance can be mounted onto a wall with the supplied mounting bracket. For a vibration-free installation, the appliance must be mounted to a solid wall with a minimum mass of 170 kg/m .
5.3 Connecting the condensate discharge The condensate discharge line for the Flair 400 is located in the lower panel. The condensate is discharged through the drainpipe. The siphon (with built-in air vent) is supplied separately with the appliance and must be fitted by the installer below the appliance (bayonet connection).
The location of the supply valves must be chosen in such a way to prevent fouling and drafts. We recommend using Brink supply valves. When using flexible mufflers, account must be taken during the installation that these may need to be replaced after a period of time.
Electrical diagram page 35); for more information and the correct modBus settings see the separate Modbus manual on the Brink website! Note: When ModBus is active, the ventilation mode cannot be changed using the display or, if applicable, the connected multiple switch! Also any connected humidity sensor will not function.
S1 / S2 = Slave appliances (For example a Flair appliance type 4-0); connect max. of 10 appliances via internal Bus. All Flair 400 appliances have the same air flow rate as the appliance that is set as "Master". The fault messages of all appliances are shown on the display of the master appliance and shown on the display of the relevant appliance.
The desired language/ date & time can be modified in the settings menu ;for this, please refer to the settings value table (® Setting values page 52, Setting values standard appliance page 52) step number 15.1 to step number 15.10. Flair 400 614895-G Brink / 19...
Filter message symbol; this is only shown if the filter has to be cleaned or replaced. See chapter "Filter cleaning" (® Cleaning filters page 29) for more information. This symbol is only shown if a fault has occurred in the appliance; see chapter Faults (® Fault analysis page 26) for more information. Flair 400 614895-G...
Page 21
This appliance is set as Master appliance if a number of appliances are connected (cascade) Appliance is set as Slave appliance; maximum of 9 appliances can be connected to a Master. Control via eBus for example Brink Air Control . Control via ModBus or internal Bus.
Page 22
Zone Symbol on display Description Internet connection/Network connection Signal strength USB connection active. 11:07 Current set time of the device. 02.01.2020 Current date. Flair 400 614895-G...
The touchscreen can also be permanently set as multiple switch; to do this step number 15.8 in the settings menu has to be set to “yes”. Warning: Incorrect settings can seriously disrupt the proper functioning of the appliance! Flair 400 614895-G Brink / 23...
1 and 3 depending on the measured PPM values: for a connected humidity sensor the air flow will be switched to mode 3 when this is switched on. Flair 400 614895-G...
Warning: As changes in the settings menu can disrupt the proper functioning of the appliance, changes of settings not described here require consultation with Brink Climate Systems B.V. Incorrect settings may seriously affect the proper performance of the appliance! 7.4 Factory settings It is possible to simultaneously revert all the changed settings back to the factory settings.
Then the appliance will reset itself (Auto reset) and the display returns to the display of the operating situation. Contact the installer to remedy this fault. 1. Supply fan defective A locking fault cannot be remedied by taking the voltage from the appliance; first the fault has to be solved. Flair 400 614895-G...
Page 27
1 E130 E1800 Relay output 1 defective; Signal output not Take voltage from appliance general fault available Replace UWA2-B pcb Fault is automatically reset when voltage is again put back on appliance. Flair 400 614895-G Brink / 27...
Page 28
Brink Air Control Check wiring to accessories/ Brink Air Control message and other Check accessories/ Brink Air Control and replace if defective accessories do If there is still a fault after this: Take voltage from appliance not work. and replace basic pcb UWA2-B...
The timer of the filter message is then reset! Pressing the Home button brings you back to the main screen from any particular menu; pressing the return button takes you back 1 step in the menu. Flair 400 614895-G Brink / 29...
9.2 Maintenance siphon Cleaning the siphon Every year the siphon must be disconnected and cleaned. (For example a Flair appliance type 4-0). Flair 400 614895-G...
Installer maintenance includes cleaning the heat exchanger, internal preheater and fans. Dependent on the conditions, this must done about once every three years. Remove the power supply by pulling out the plug. Open the filter door. Remove the two filters. Remove the front cover. Flair 400 614895-G Brink / 31...
Page 32
Remove the heat exchanger. Be careful not to damage the foam parts in the appliance. Wash the heat exchanger with hot water (max. 45°C) and a regular detergent. Then rinse the exchanger with hot water. Take EPS assembly, with which the fan is inserted into the appliance, out of the appliance. Flair 400 614895-G...
Page 33
Tilt the fan in such a way that this can be taken out of the EPS assembly; disconnect both fan cables from the fan. Now take the fan out of the appliance. Repeat steps 6 to 9 for the other fan in the appliance. Flair 400 614895-G Brink / 33...
Page 34
Reset the timer of the filter message by setting the timer back to zero in the settings menu at step number 4.3. After resetting the timer of the filter message the appliance returns to the main menu and the appliance is once again ready for use. Flair 400 614895-G...
Page 36
USB stick for updating software (not supplied with appliance) X18 = 24V (max 5VA) Service connector X19 = Signal output Laptop with installed Brink service tool (not supplied) Plus pcb (option) Touchscreen on appliance Valve motor bypass valve X03 = 24V...
It is best to use a 4-way switch with filter indication; always install an RJ12 connector in combination with a 6- core modular cable. When using a 3-way switch without filter indication always install an RJ11 connector in combination with a 4-core modular cable. Flair 400 614895-G Brink / 37...
C = Modular cable: Note: For the modular cable that is used, the “tab” of both modular connectors must be mounted facing the mark on the modular cable. Wire colors C1 - C6 may vary dependent on the type of modular cable used. Flair 400 614895-G...
F = Modular cable: Note: For the modular cable that is used, the “tab” of both modular connectors must be mounted facing the mark on the modular cable. Wire colors C1 - C6 may vary dependent on the type of modular cable used. Flair 400 614895-G Brink / 39...
= Modular cable: Note: For the modular cable that is used, the “tab” of both modular connectors must be mounted facing the mark on the modular cable. Wire colors C1 - C6 may vary dependent on the type of modular cable used. Flair 400 614895-G...
F = Modular cable: Note: For the modular cable that is used, the “tab” of both modular connectors must be mounted facing the mark on the modular cable. Wire colors C1 - C6 may vary dependent on the type of modular cable used. Flair 400 614895-G Brink / 41...
11.2 Connecting Brink Air Control A = Flair appliance (For example a Flair appliance type 4-0) B = Brink Air Control (option) C = Two-core control cables D = Green two-pole screw connector E = Position green eBus connector to rear of control...
4 = The cable that comes with RH cable 5 = RH (humidity) sensor 6 = Duct from dwelling To switch on and set the sensitivity of the humidity sensor, go to step number 7.1 and 7.2 in the settings menu Flair 400 614895-G Brink / 43...
6.1 in the settings menu ; in order to set the minimum and maximum PPM value of the CO sensor(s) set, if necessary, the right values following step numbers 6.2 to 6.9. Flair 400 614895-G...
For further information regarding setting, operating and connecting demand-driven ventilation 2.0, refer to the installation instructions supplied with the demand-driven device. 1 = Zone valve demand-driven ventilation 2 = Power 24 VDC 3 = Brink Air Control C1 =brown C2 = blue 4 = Valve motor zone valve...
C2 = blue 4 = Temperature sensor C3 = green/yellow C4 = black 5 = PCB type UVP1 C5 = white 6 = Airflow direction 7 = Dipswitch setting Flair postheater (For example a Flair appliance type 4-0) Flair 400 614895-G...
N.B.: Appliance type, serial number and year of production are stated on the identification plate behind the plastic front panel on the appliance. Example Appliance type Flair 450 Serial number 43100022201 Year of production 2022 Part Article code 532770 Quantity Flair 400 614895-G Brink / 49...
Page 51
The power cable is fitted with a circuit board connector. When replacing it, always order a replacement mains cable from Brink. To prevent dangerous situations, a damaged mains connection can only be replaced by a qualified expert. Flair 400 614895-G Brink / 51...
13 Setting values 13.1 Setting values standard appliance The below setting values are for a Flair 400-appliance without Plus pcb. Step Description Factory settings Setting range Comment Flow rate Air flow rate setting 0 50 m³/h 0 or adjustable between 50 m³/h and 400 m³/h (never higher than step no.
Page 53
(0=Master; 1 t/m 9 = Slave 1 t/m Slave 9) Central heating + heat recovery 12.1 Status On / Off Communication 14.1 Type of Bus connection ModBus Off / ModBus/ internal Bus 14.2 Slave address 1 - 247 For Modbus Flair 400 614895-G Brink / 53...
Page 54
Yes / No 15.10 Fan position wizard Yes / No Signal output 16.1 Signal output Off / Only filter condition / Only fault Connector X19 condition / Filter and fault condition Standby 17.1 Switch off appliance Yes / No Flair 400 614895-G...
13.2 Setting values appliance with Plus pcb The below setting values are for a Flair 400-appliance with Plus pcb. Step Description Factory settings Setting range Comment Switch contacts Make or break contact 1 Make Make / Break Switch contact control 1...
Page 56
Switch temperature 2 25 °C 15.0°C / 40.0 °C 11.4 Mode valve 24 volt control Closed Open / Closed 11.5 Valve control Relay output 1 Relay output 1/ Relay output 2/ Analogue output 1/ Analogue output 2 Flair 400 614895-G...
14 Conformity declaration This declaration of conformity is issued under the sole responsibility of the manufacturer. Manufacturer: Brink Climate Systems B.V. P.O. Box 11 Address: NL-7950 AA, Staphorst, The Netherlands Product: Flair 400 The product described above complies with the following directives: ¨...
15 ERP values Technical information sheet Flair 400 in accordance with Ecodesign (ErP), no. 1254/2014 (Annex IV) Manufacturer: Brink Climate Systems B.V. Model: Flair 400 Climate Type of control SEC Value in Annual Annual heating zone kWh/m²/a Class electricity saved (AHS) in...
16 Recycling Recycling Sustainable materials are used in the manufacture of this appliance. The packaging should be disposed of in a responsible manner and in accordance with governmental regulations. Flair 400 614895-G...