Electric Connections Accessories - Brink Renovent Excellent 180 Installation Instructions Manual

Heat recovery appliance
Hide thumbs Also See for Renovent Excellent 180:
Table of Contents

Advertisement

11.1 Connections connectors
1
2
3
4
26
Chapter 11

Electric connections accessories

5
6
7
Renovent Excellent 180
Power supply cable 230 V
1
eBus connector
2
Two-pole screw connector
Only suitable for low voltage.
Note: This connector is polarity sensitive.
Modular connector for rpm control
3
Modular connector type RJ-12
Only suitable for low voltage!
Service connector
4
Computer connection for service purposes
Extra cable gland
5
Gland for 230 V cable from X14 when connecting a postheat-
er or 230 V cable from f X12 for preheater. Always use a strain
reliever.
Extra cable gland
6
Gland low voltage cable, for instance for installation of an RH
(humidity) sensor. Cut out an opening in the available grom-
met for feeding through the cable.
9-pole connector (only for Plus version)
7
Connection Application
1 & 2
Step no. 15 = 0: NO contact
(input 1)
Step no. 15 = 1: 0 - 10 V input; X15-1= GND
Step no. 15 = 2: NC contact
Step no. 15 = 3: switching output 1:
Step no. 15 = 4: switching output 1:
3 & 4
Step no. 21 = 0: NO contact
Step no. 21 = 1: 0 - 10 V input
(input 2)
Step no. 21 = 2: NC contact
Step no. 21 = 3: switching output 2:
Step no. 21 = 4: switching output 2:
5 & 6
Connection 24 V,
Max. 4.5 VA; (5 = ground , 6 = +)
7 & 8
Connection postheater sensor or and
outdoor geo-heat exchanger
9
Control signal valve 0 or 10 V
( 9 = +, 5 = ground)
Rev. E
(= factory setting) §11.6)
& 15-2=0-10 V (see §11.7)
bypass function active
12V;
bypass function not active 0V
bypass function active
0V;
bypass not active
12V
(= factory setting) see §11.7.
bypass function active
12V;
bypass not active
0V
bypass function active
0V;
bypass not active
12V

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Renovent excellent 180 plus

Table of Contents