Brink Renovent Sky 300 Installation Instructions Manual

Brink Renovent Sky 300 Installation Instructions Manual

Hide thumbs Also See for Renovent Sky 300:

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
(English)
WWW.BRINKAIRFORLIFE.NL
612378-G

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Renovent Sky 300 and is the answer not in the manual?

Questions and answers

Summary of Contents for Brink Renovent Sky 300

  • Page 1 INSTALLATION INSTRUCTIONS (English) WWW.BRINKAIRFORLIFE.NL 612378-G...
  • Page 3 Renovent Sky 300 (Plus) STORE NEAR THE APPLIANCE This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
  • Page 4: Table Of Contents

    Table of contents page. Delivery..................................Scope of delivery ................................ Accessories Renovent Sky 300 ..........................Application ................................4 Version..................................Technical information ..............................Connections and dimensions ............................. Fan graph ................................... Exploded view appliance ............................Operation ................................... Description.................................. Bypass conditions............................... Frost safety .................................
  • Page 5: Delivery

    Scope of delivery Before starting installation of the heat recovery unit, check that it has been supplied complete and undamaged. The scope of delivery of the heat recovery unit Renovent Sky 300 includes the following components: 1: Heat recovery appliance 2: Wall mounting bracket kit;...
  • Page 6: Accessories Renovent Sky 300

    Transmitter wireless remote control 4 positions (with. battery) 532171 Receiver wireless remote control (for battery version) 532172 Kit wireless remote control 2 positions (1 transmitter & 1 receiver) 532173 Kit wireless remote control 4 positions (1 transmitter & 1 receiver) 532174 Renovent Sky 300 Rev. G...
  • Page 7 532002 Servicetool 531961 Enthalpie heat exchanger 532060 Demperunit 2 x Ø160 mm 422500 Demperunit 18 x Ø75 mm 422501 Demperunit 18 x 100 - 50 mm 422502 Demperunit 12 x 130 - 60 mm 422503 Renovent Sky 300 Rev. G...
  • Page 8: Application

    The Renovent Sky 300 comes ready to plug in with a 230 V mains plug. The appliance comes as standard with a “Brink Air Control”, but connection of a simple 4-way switch is possible as well.
  • Page 9: Version

    Ventilation capacity [m Static pressure [Pa] Housing emission [dB(A)] Sound power level Lw (A) Duct “from dwelling” [dB(A)] Duct “to dwelling” [dB(A)] In practice, the value may deviate 1 dB(A) as a result of measuring tolerances. Renovent Sky 300 Rev. G...
  • Page 10: Connections And Dimensions

    1 To dwelling 2 To atmosphere 3 From dwelling 4 From atmosphere 5 Electric connections 6 Connection condensate discharge Fan graph Note: The value stated in the circle is the ca- pacity per fan (in Watt) Renovent Sky 300 Rev. G...
  • Page 11: Exploded View Appliance

    15 9-pole connector (only for Plus version) 16 Service connector 17 Connection 230V preheater 18 Modular connector multiple switch 19 Connector eBus 20 Mains cable 230 V. 21 Fall protection front panel 22 Mounting strip Renovent Sky 300 Rev. G...
  • Page 12: Operation

    See §9 for more information on the connection possibilities of connectors X14 and X15. Hole for gland to be mounted by installer (for sleeve cable postheater/ extra preheater). Renovent Sky 300 Rev. G...
  • Page 13: Installation

    The Renovent Sky 300 can directly be mounted to the wall or the condensate discharge ceiling using the mounting brackets supplied for that purpose. possible to replace them in due course.
  • Page 14: Placing The Appliance For Ceiling Mounting

    Chapter 5 Installation Click! Appliance disconnecting from mounting bracket Condensate discharge Renovent Sky 300 Rev. G...
  • Page 15: Placing The Appliance For Wall Mounting

    Chapter 5 Installation m i n . 2 5 m 4 9 0 m i n . 2 5 m 2 0 0 m 6 5 0 Click! Appliance disconnecting from mounting bracket Condensate discharge Renovent Sky 300 Rev. G...
  • Page 16: Connecting The Condensate Discharge

    Before connecting the condensate discharge to the appliance, pour water into the U-trap to create an air trap. of the sleeve connection when servicing the appli- ance! Ø 32 mm example outside diameter Detachable coupler Detachable coupler Renovent Sky 300 Rev. G...
  • Page 17 Chapter 5 Installation 60 mm Renovent Sky 300 Rev. G...
  • Page 18 Chapter 5 Installation 60 mm Renovent Sky 300 Rev. G...
  • Page 19: Electric Connections

    2000 W. The “Brink Air Control” that comes as standard with the appli- able) 2-pole eBus connector is mounted on the outside of the ance must be connected to the eBus connector. This (detach- appliance (see also §10.1).
  • Page 20: Display

    The “Brink Air control” display shows what the operating mode the operating keys. Ex factory the “Brink Air Control” is set for of the appliance is. Settings in the “Brink Air control” software of the English language. In the setting menu “Brink Air Control”, the Renovent Sky can be called up and changed with the aid of §6.4.2, you can choose a language.
  • Page 21: View On Display

    Chapter 6 Display View on Display When the Renovent Sky is in operating mode, the “Brink Flow rate indicator 10.54 01.03.16 Fan indicator HRU-Ventilation 0 8 :0 0 17:0 0 Filter message Filter Flow rate indicator 4-way switch The supply and extract fans are running at 50 m /h or they are stopped (step number 1).
  • Page 22: Main Menu

    Chapter 6 Display Main menu Pressing the right-hand setting knob on the “Brink Air control” takes you to the MAIN MENU 10.54 23/11/15 In this main menu you can use the right-hand setting knob to HRU-Ventilation 0 8 :0 0 17:0 0 select one of the 3 available manuals (rotate to select and press - Device information §6.4.1...
  • Page 23: 6.4.1 Device Information Menu

    Airflow extract 0 m³/h Airflow extract 0 m³/h T dwelling 20.0 °C T dwelling 20.0 °C T atmosphere 15.3 °C T atmosphere 15.3 °C 0.0 % 0.0 % CO2-Sensor 1 CO2-Sensor 2 CO2-Sensor 3 CO2-Sensor 4 Renovent Sky 300 Rev. G...
  • Page 24: Basic Settings Menu

    Basic settings - Language Installer - Date - Key lock Language In this menu you can choose a language; ex factory the “Brink Air Control” is set for the English language. The optional languages are: Dutch 10.56 01.03.16 10.58 01.03.16...
  • Page 25: 6.4.3 Installer Menu

    Min. PPM ebus CO2-Sensor 3 Max.PPM ebus CO2-Sensor 3 Min. PPM ebus CO2-Sensor 4 Max.PPM ebus CO2-Sensor 4 Offset flow Default position switch 10.59 01.03.16 Airflow - mode 0 50m³/h Standard: 50 m³/h Range: 0 or 50 m³/h Renovent Sky 300 Rev. G...
  • Page 26: Fault

    Chapter 7 Fault When the appliance control system detects a fault, it is indi- cated on the display of the “Brink Air control” with a spanner symbol, possibly together with a fault code. Non-locking fault 10.59 01.03.16 Messages HRU-appliance History of errors 10.54...
  • Page 27: Display Codes

    (see § 9). either. Note! If mode 2 of a multiple switch does not work, the modular connector of the multiple switch has been connected the wrong way round. Renovent Sky 300 Rev. G...
  • Page 28: Maintenance

    ISO Coarse 60% (G4) 10.54 01.03.16 HRU-Ventilation 0 8 :0 0 17:0 0 Filter 10.54 01.03.16 HRU-Ventilation Manual Filter ca. 10 sec. ISO Coarse 60% (G4) / ISO ePM 1 50% (F7) 10.54 01.03.16 HRU-Ventilation Manual Filter Renovent Sky 300 Rev. G...
  • Page 29 Chapter 8 Maintenance Click! 10.54 01.03.16 HRU-Ventilation Manual Filter 5 sec. Filter reset 10.54 01.03.16 HRU-Ventilation 0 8 :0 0 17:0 0 Renovent Sky 300 Rev. G...
  • Page 30: Maintenance Installer

    Chapter 8 Maintenance Maintenance installer Swing open the front panel (can also be taken from the hinges, if required). Renovent Sky 300 Rev. G...
  • Page 31 Chapter 8 Maintenance max.45 ºC Rinse the exchanger with hot water and a regular detergent. Renovent Sky 300 Rev. G...
  • Page 32 Chapter 8 Maintenance Renovent Sky 300 Rev. G...
  • Page 33 S1.01.01 > ± 25 sec 10.54 23/11/15 HRU-Ventilation 08:00 17:00 Filter reset; see §8.1 point 6 Press the Return key ( ) to leave any selected menu and the appliance will return to operating mode. Renovent Sky 300 Rev. G...
  • Page 34: Elektric Diagram

    Motor bypass pre-heater temperature extract fan temperature switch board connector valve sensor sensor external “Brink Air sensor 0-10 V RH-sensor post-heater output 0-10V 24V. switch (optional) Control” applicable post-heater input contact Renovent Sky 300 Rev. G...
  • Page 35: Elektrische Aansluitingen Acc

    1 or 2. The boost mode can be reset by putting the switch to setting 3 for longer than 2 seconds or by switching it to absence mode ( Renovent Sky 300 Rev. G...
  • Page 36: Connection Rh (Humidity)-Sensor

    X1-1 and contacts X1-2 to X1-2. Never connect X1-1 and There must be a separate 230 volt wall socket for every appli- X1-2. A maximum of 10 appliances (1 Master + 9 Slave max.) Master Slave 1 nr.1 nr.2 Renovent Sky 300 Rev. G...
  • Page 37: Connection Preheater

    The strain reliever to be installed by the installer (not supplied with the appliance) for feeding the 230 volt cable to the pos- theater or extra preheater. 230V 50Hz 230V 50Hz Temperature sensor postheater 7 - 8. Renovent Sky 300 Rev. G...
  • Page 38: Connection Geo Heat Exchanger

    Chapter 10 Electric connections accessories 30°C Minimum temperature 25°C Maximum temperature To dwelling To atmosphere From dwelling From atmosphere 15°C 10°C 3°C 0°C Setting parameter 26, 27 & 28 (§12) Renovent Sky 300 Rev. G...
  • Page 39: Connecting External Switch Contact

    Connections no. 3 and no. 4 standard 0-10 volt input; connections no. 1 and no. 2 can optionally be used as 0-10 volt input as well. Setting parameter 20, 21 & 22 (§12) Renovent Sky 300 Rev. G...
  • Page 40: Service

    Serial number : 422004184301 name of the part:: Year of production : 2018 Part : Fan Appliance type, serial number and year of production are Article code : 531774 11.2 Service parts Renovent Sky 300 Rev. G...
  • Page 41 Control board UWA-01 (Plus version) When replacing, note the correct dip switch settings. 531780 Cable with power plug 230 volt * 531978 Mounting strip 530510 The mains cable has a print connector. When replacing it, always order a replacement mains cable Brink without prior notice. Renovent Sky 300 Rev. G...
  • Page 42: Setting Values

    4 (= Bedroom valve) 2 (= Flow rate mode 1) Supply fan mode 3 (= Flow rate mode 2) switching input 1 4 (= Flow rate mode 3) 5 (= Multiple switch 7 (= No input fan activation) Renovent Sky 300 Rev. G...
  • Page 43 5,0 °C 0,0 °C - 10,0 °C 0,5 °C (Below this temperature the valve opens.) Maximum temperature geo heat exchanger 25,0 °C 15,0 °C - 40,0 °C 0,5 °C (Above this temperature the valve opens.) Renovent Sky 300 Rev. G...
  • Page 44 Max. PPM eBus CO -sensor 4 1200 Flow correction 100% 90% - 110% Default position switch 0 - 1 RENO- ADJUSTING RANGE Brink Connect function (exter- nal, Brink connect no RH sen- Brink Connect sor) Brink Connect (internal) Renovent Sky 300 Rev. G...
  • Page 45: Erp-Values

    0,65 in combination with l ocal demand control with at least two or more sensors and with at least a two-zone control Internal 0,9% Leakage*: External 2,0% On the Manual switch / “Brink Air Control” Filterwarning: Attention! cleaning or replacement is necessary. Internet address for Assembly instructions: http://www.brinkclimatesystems.nl/installateurs/kenniscentrum/Documentatie.aspx Bypass: Yes;...
  • Page 46: Declaration Of Conformity

    The product described above complies with following directives: 2014/35/EU (low voltage directive) 2014/30/EU (EMC directive) RoHS 2011/65/EU (substances directive) 2009/125/EG (1253/1254 EU (EU ErP- directive)) The product bears the CE label: Staphorst, 05-01-12 W. Hijmissen, Managing director Renovent Sky 300 Rev. G...
  • Page 48 BRINK CLIMATE SYSTEMS B.V. P.O. Box T. +31 (0) 522 46 99 44 F. +31 (0) 522 46 94 00...

This manual is also suitable for:

Renovent sky 300 plus