Renovent Sky 300 (Plus) STORE NEAR THE APPLIANCE This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
Scope of delivery Before starting installation of the heat recovery unit, check that it has been supplied complete and undamaged. The scope of delivery of the heat recovery unit Renovent Sky 300 includes the following components: 1: Heat recovery appliance 2: Wall mounting bracket kit;...
The Renovent Sky 300 comes ready to plug in with a 230 V mains plug. The appliance comes as standard with a “Brink Air Control”, but connection of a simple 4-way switch is possible as well.
Ventilation capacity [m Static pressure [Pa] Housing emission [dB(A)] Sound power level Lw (A) Duct “from dwelling” [dB(A)] Duct “to dwelling” [dB(A)] In practice, the value may deviate 1 dB(A) as a result of measuring tolerances. Renovent Sky 300 Rev. G...
1 To dwelling 2 To atmosphere 3 From dwelling 4 From atmosphere 5 Electric connections 6 Connection condensate discharge Fan graph Note: The value stated in the circle is the ca- pacity per fan (in Watt) Renovent Sky 300 Rev. G...
See §9 for more information on the connection possibilities of connectors X14 and X15. Hole for gland to be mounted by installer (for sleeve cable postheater/ extra preheater). Renovent Sky 300 Rev. G...
The Renovent Sky 300 can directly be mounted to the wall or the condensate discharge ceiling using the mounting brackets supplied for that purpose. possible to replace them in due course.
Chapter 5 Installation m i n . 2 5 m 4 9 0 m i n . 2 5 m 2 0 0 m 6 5 0 Click! Appliance disconnecting from mounting bracket Condensate discharge Renovent Sky 300 Rev. G...
Before connecting the condensate discharge to the appliance, pour water into the U-trap to create an air trap. of the sleeve connection when servicing the appli- ance! Ø 32 mm example outside diameter Detachable coupler Detachable coupler Renovent Sky 300 Rev. G...
2000 W. The “Brink Air Control” that comes as standard with the appli- able) 2-pole eBus connector is mounted on the outside of the ance must be connected to the eBus connector. This (detach- appliance (see also §10.1).
The “Brink Air control” display shows what the operating mode the operating keys. Ex factory the “Brink Air Control” is set for of the appliance is. Settings in the “Brink Air control” software of the English language. In the setting menu “Brink Air Control”, the Renovent Sky can be called up and changed with the aid of §6.4.2, you can choose a language.
Chapter 6 Display View on Display When the Renovent Sky is in operating mode, the “Brink Flow rate indicator 10.54 01.03.16 Fan indicator HRU-Ventilation 0 8 :0 0 17:0 0 Filter message Filter Flow rate indicator 4-way switch The supply and extract fans are running at 50 m /h or they are stopped (step number 1).
Chapter 6 Display Main menu Pressing the right-hand setting knob on the “Brink Air control” takes you to the MAIN MENU 10.54 23/11/15 In this main menu you can use the right-hand setting knob to HRU-Ventilation 0 8 :0 0 17:0 0 select one of the 3 available manuals (rotate to select and press - Device information §6.4.1...
Basic settings - Language Installer - Date - Key lock Language In this menu you can choose a language; ex factory the “Brink Air Control” is set for the English language. The optional languages are: Dutch 10.56 01.03.16 10.58 01.03.16...
Chapter 7 Fault When the appliance control system detects a fault, it is indi- cated on the display of the “Brink Air control” with a spanner symbol, possibly together with a fault code. Non-locking fault 10.59 01.03.16 Messages HRU-appliance History of errors 10.54...
(see § 9). either. Note! If mode 2 of a multiple switch does not work, the modular connector of the multiple switch has been connected the wrong way round. Renovent Sky 300 Rev. G...
Page 33
S1.01.01 > ± 25 sec 10.54 23/11/15 HRU-Ventilation 08:00 17:00 Filter reset; see §8.1 point 6 Press the Return key ( ) to leave any selected menu and the appliance will return to operating mode. Renovent Sky 300 Rev. G...
1 or 2. The boost mode can be reset by putting the switch to setting 3 for longer than 2 seconds or by switching it to absence mode ( Renovent Sky 300 Rev. G...
X1-1 and contacts X1-2 to X1-2. Never connect X1-1 and There must be a separate 230 volt wall socket for every appli- X1-2. A maximum of 10 appliances (1 Master + 9 Slave max.) Master Slave 1 nr.1 nr.2 Renovent Sky 300 Rev. G...
The strain reliever to be installed by the installer (not supplied with the appliance) for feeding the 230 volt cable to the pos- theater or extra preheater. 230V 50Hz 230V 50Hz Temperature sensor postheater 7 - 8. Renovent Sky 300 Rev. G...
Chapter 10 Electric connections accessories 30°C Minimum temperature 25°C Maximum temperature To dwelling To atmosphere From dwelling From atmosphere 15°C 10°C 3°C 0°C Setting parameter 26, 27 & 28 (§12) Renovent Sky 300 Rev. G...
Connections no. 3 and no. 4 standard 0-10 volt input; connections no. 1 and no. 2 can optionally be used as 0-10 volt input as well. Setting parameter 20, 21 & 22 (§12) Renovent Sky 300 Rev. G...
Serial number : 422004184301 name of the part:: Year of production : 2018 Part : Fan Appliance type, serial number and year of production are Article code : 531774 11.2 Service parts Renovent Sky 300 Rev. G...
Page 41
Control board UWA-01 (Plus version) When replacing, note the correct dip switch settings. 531780 Cable with power plug 230 volt * 531978 Mounting strip 530510 The mains cable has a print connector. When replacing it, always order a replacement mains cable Brink without prior notice. Renovent Sky 300 Rev. G...
Page 43
5,0 °C 0,0 °C - 10,0 °C 0,5 °C (Below this temperature the valve opens.) Maximum temperature geo heat exchanger 25,0 °C 15,0 °C - 40,0 °C 0,5 °C (Above this temperature the valve opens.) Renovent Sky 300 Rev. G...
Page 44
Max. PPM eBus CO -sensor 4 1200 Flow correction 100% 90% - 110% Default position switch 0 - 1 RENO- ADJUSTING RANGE Brink Connect function (exter- nal, Brink connect no RH sen- Brink Connect sor) Brink Connect (internal) Renovent Sky 300 Rev. G...
0,65 in combination with l ocal demand control with at least two or more sensors and with at least a two-zone control Internal 0,9% Leakage*: External 2,0% On the Manual switch / “Brink Air Control” Filterwarning: Attention! cleaning or replacement is necessary. Internet address for Assembly instructions: http://www.brinkclimatesystems.nl/installateurs/kenniscentrum/Documentatie.aspx Bypass: Yes;...
The product described above complies with following directives: 2014/35/EU (low voltage directive) 2014/30/EU (EMC directive) RoHS 2011/65/EU (substances directive) 2009/125/EG (1253/1254 EU (EU ErP- directive)) The product bears the CE label: Staphorst, 05-01-12 W. Hijmissen, Managing director Renovent Sky 300 Rev. G...
Page 48
BRINK CLIMATE SYSTEMS B.V. P.O. Box T. +31 (0) 522 46 99 44 F. +31 (0) 522 46 94 00...