I/O expansion module LED faults and remedy

Table 30: Baseboard communication fail
Description
Baseboard Communication Fail
• Verify jumper JP8 on main board is shorted.
• Verify connection of cable between H5 on main board and H1 on I/O expansion board.
Table 31: Compressor #2 high pressure
Description
Compressor #2 High Pressure
• Verify high pressure switch is connected to terminal HP2 on the I/O expansion.
• Check for continuity of the high pressure switch.
If the high pressure fault resets when power is recycled:
• Check water flow (cooling operation)
• Check airflow (heating operation)
• Entering water and air temperatures should be within the operating limits
Table 32: Compressor #2 low pressure
Description
Compressor #2 Low Pressure
• Loose wire connection on low pressure circuit
• Failed low pressure switch
• Circuit #2 is low on charge
Table 33: Compressor #2 low suction temp
Description
Compressor #2 Low Suction Temp
• Check water flow (heating operation)
• Check airflow (cooling operation)
• Entering water and air temperatures should be within the operating limits.
Table 34: Compressor #2 low suction temp
Description
Compressor #2 Low Suction Temp
• Check water flow (heating operation)
• Check airflow (cooling operation)
• Entering water and air temperatures should be within the operating limits.
Table 35: Compressor suction temp sensor fail
Description
Compressor Suction Temp Sensor
Fail
• Check connection of low suction temperature sensor on terminal H7 pins 1 and 2.
• Check resistance of low suction temperature sensor. All sensors are 10kohm thermistor @77°F.
Table 36: Entering water temp sensor fail (boilerless electric heat or waterside economizer only)
Description
Entering Water Temp Sensor Fail
(Boilerless Electric Heat or Waterside
Economizer Only)
• Verify connections at terminals H4 on the I/O expansion board
• Verify resistance of EWT thermistor is 10K @ 77°F.
www.DaikinApplied.com
Type
Yellow
Fault
Flash
Type
Yellow
Fault
OFF
Type
Yellow
Fault
OFF
Type
Yellow
Fault
Flash
Type
Yellow
Fault
Flash
Type
Yellow
Fault
Flash
Type
Yellow
Fault
ON
45
t
roubleshooting
Green
Red
OFF
Flash
Green
Red
OFF
Flash
Green
Red
OFF
ON
Green
Red
OFF
OFF
Green
Red
OFF
OFF
Green
Red
OFF
OFF
Green
Red
OFF
Flash
LARGE VERTICAL WSHP IM 1059-12