Installation Considerations; Unit Location; Fan Deck Arrangements - Daikin Enfinity Installation And Maintenance Manual

Large capacity vertical water source heat pumps
Table of Contents

Advertisement

Unit location

Large Vertical Water Source Heat Pump units are easily
located in equipment rooms or floor-by-floor installations.
They can be applied to all building types where it is
advantageous to extend the water source heat pump
concept to larger or core areas.
Locate the unit in an area that allows for easy removal
of the filter and access panels, and has enough space
for service personnel to perform maintenance or repair.
Provide sufficient room to make water, electrical and
duct connections.
Figure 1: Service clearances
Notes 1. A 12" (305 mm) minimum clearance is re-
quired on the side opposite the pipe connec-
tion side to gain access to panel to remove
locking collar for shaft removal.
2. Top clearance is required for fan shaft removal.
The contractor should make sure that access has been
provided including clearance for 2" (51 mm) thick filter
brackets, duct collars and fittings at water and electrical
connections. Allow adequate room around the unit
for a condensate trap. The unit can be installed "free
standing" in an equipment room. Generally, the unit is
located in a separate room with the non-ducted return air
facing the return air intake.
Alternatively, the unit can have a ducted return air. It is
recommended that the unit be located on vibration isolators
to reduce any vibration (see

Fan deck arrangements

Six fan discharge arrangements and two piping
arrangements are available. With the return air side
defined as the "front" of the unit, the water piping
connections may be right-hand (side) or left-hand. All units
have a single supply and return water connection with
a copper FPT type fitting that protrudes through the unit
casing for easy connection. The condensate connection is
www.DaikinApplied.com
Figure 3 on page
6).
also a copper FPT type and is located on both sides of the
unit. The unused connection is plugged.
The main control panel is located in the center front of
the unit. The fan discharge is top front, and the fan motor
is always located at the piping end. Unit sides opposite
the control panel and opposite the piping side may be up
against walls and still allow for service and maintenance
through the remaining access panels.
Figure 2: Fan deck arrangements
Rear (or Top)
Discharge
Right-Hand Piping
(Upblast-Rear)
Rear (or Top)
Straight Horizontal
Discharge
Discharge Left-Hand
Left-Hand Piping
Piping (Top-Horizontal
(Upblast & Rear)
Notes: 1. The hand of unit is determined by looking
at the return air (filter) side. The piping and
electrical connections are always made on
the "hand" side of the unit. The return air (fil-
ter) side is considered the "front" of the unit.
2. The fan motor is always located at the piping/
electrical connection (hand) side of the unit.
5
i
C
nstallation
onsiderations
Fan
Motor
Front (or Top)
Front (or Top)
Discharge
Discharge
Left-Hand Piping
Right-Hand Piping
(Upblast-Front)
(Upblast-Front)
Straight Horizontal
Discharge Right-Hand
Piping (Top-Horizontal
Discharge)
Discharge)
LARGE VERTICAL WSHP IM 1059-12

Advertisement

Table of Contents
loading

Table of Contents