Vibration isolators

For minimum sound and vibration transmission, it is
recommended that the unit be mounted on vibration
isolators.
Holes are provided in the bottom panel to facilitate
connection of isolators (see
Isolators supplied by the manufacturer are the type
shown in
Figure
3. Four white isolators are used for single
compressor units and six green isolators are used for
dual compressor units. The holes in the bottom of the unit
allow for a 3⁄8" (10 mm) bolt to be secured to the isolator.
Figure 4: Vibration isolators locations - single compressor unit
3"
(76 mm)
28
5
/
"
32
(715 mm)
3" (76 mm)
Figure 5: Vibration isolators locations - dual compressor unit
2"
(51 mm)
30
1
/
"
8
(765 mm)
2" (51 mm)
IM 1059-12 LARGE VERTICAL WSHP
Figure 4
& 5 for hole locations).
(4)
7
/
" (11 mm) holes
16
3" (76 mm)
54
23
/
"
32
(1390 mm)
3
1
/
" (83 mm)
4
Figure 3: Vibration isolator dimensions
2⅝" (61 mm)
7/16" (11 mm)
A
A
3" (76 mm)
(6)
3
/
" (19 mm) holes
8
40
3
/
"
16
(1021 mm)
80
3
/
"
8
(2042 mm)
6
i
C
nstallation
onsiderations
3/8" (10 mm) TAP
2½" (64 mm)
7
/
"
16
(11 mm)
2"
1
/
"
4
(51 mm)
(6 mm)
Section A-A
3
1
/
" (83 mm)
4
www.DaikinApplied.com