Microtech Iii Unit Controller And I/O Expansion Module Terminals, Locations And Descriptions - Daikin Enfinity Installation And Maintenance Manual

Large capacity vertical water source heat pumps
Table of Contents

Advertisement

MicroTech III unit controller and
I/O expansion module terminals,
locations and descriptions
Table 12: MicroTech III unit controller terminals locations
and descriptions
H1 – 1
24
24 VAC Power Input
H1 – 2
C
24 VAC common
H2 – 1
SL1
Fan Main Output – Switched L1
H2 – 2
Blank Terminal
H2 – 3
N
Fan Main Output – Neutral
H3 – 1
HP1-1
Comp High Pressure Switch (HP1) Input Terminal 1
H3 – 2
HP1-2
Comp High Pressure Switch (HP1) Input Terminal 2
H4 – 1
1
Discharge Air Temp Sensor – Common
H4 – 2
Discharge Air Temp Sensor – Signal
H4 – 3
Leaving Water Temp Sensor – Common
H4 – 4
Leaving Water Temp Sensor – Signal
H5 – 1
1
I/O Expansion Module Common (Gnd)
H5 – 2
I/O Expansion Module Common (Gnd)
H5 – 3
I/O Expansion Module +5 VDC
H5 – 4
I/O Expansion Module SPI CE1
H5 – 5
I/O Expansion Module SPI CLK
H5 – 6
I/O Expansion Module SPI OUT
H5 – 7
I/O Expansion Module SPI IN
H5 – 8
I/O Expansion Module +12 VDC
H5 – 9
I/O Expansion Module 24 VAC
H5 – 10
I/O Expansion Module 24 VAC
H5 – 11
No Connection
H5 – 12
No Connection
H6 – 1
1
Condensate Overflow Signal Input
H6 – 2
Compressor Suction Temp Sensor (LT1) – Common
H6 – 3
Compressor Suction Temp Sensor (LT1) – Signal
Compressor Low Pressure Switch (LP1) –
H6 – 4
Source Voltage
H6 – 5
Compressor Low Pressure Switch (LP1) – Signal
H6 – 6
Reversing Valve – Common
H6 – 7
Reversing Valve – Output
H7 – 1
1
No Connection
H7 – 2
No Connection
H7 – 3
Red LED Output
www.DaikinApplied.com
H7 – 4
Green LED Output
H7 – 5
Yellow LED Output
H7 – 6
Red-Green-Yellow LED Common
H8 – 1
1
Isolation Valve/Pump Request Relay N/O
H8 – 2
Isolation Valve/Pump Request Relay N/C
H8 – 3
24 VAC Common
H9 – 1
1
Return Air Temp – Signal
H9 – 2
Return Air Temp* – Common
TB1 – 1
1
Room Sensor – Status LED Output
TB1 – 2
2
Room Sensor – Fan Mode & Unit Mode Switches
TB1 – 3
3
Room Sensor – Setpoint Adjust Potentiometer
Room Sensor – Room Temp Sensor & Tenant
TB1 – 4
4
Override
TB1 – 5
5
Room Sensor – DC Signal Common
TB2 – 1
R
24 VAC
TB2 – 2
A
Alarm Output
TB2 – 3
W2
Thermostat – Heat Stage #2 (W2) Input
TB2 – 4
W1
Thermostat – Heat Stage #1 (W1) Input
TB2 – 5
Y2
Thermostat – Cool Stage #2 (Y2) Input
TB2 – 6
Y1
Thermostat – Cool Stage #1 (Y1) Input
TB2 – 7
G
Thermostat – Fan Input
TB2 – 8
O
Thermostat – Heat Stage #3 (W3) Input
TB2 – 9
C
24 VAC Common
TB3 – 1
E
Emergency Shutdown Input
TB3 – 2
U
Unoccupied Input
L1 – 1
L1 - 1
L1 – 2
L1 - 2
24 VAC Power in
L1 – 3
L1 - 3
N1
N1
N2
N2
24 VAC Common
N3
N3
CN_LON1 – 1 CN_LON1 GND
CN_LON1 – 2
+ 5 VDC
CN_LON1 – 3
SPI CE (SPI Select To Communications Board)
CN_LON1 – 4
SPI CLK (Master Clock)
CN_LON1 – 5
SPI OUT (MOSI)
CN_LON1 – 6
SPI IN (MISO)
CN_LON1 – 7
INT0 (SPI Ready To Baseboard)
CN_LON1 – 8
No Connection
* Can have return air temperature sensor connected at H9 while the
room sensor is connected to TB1, pin 4 (room temp sensor and ten-
ant override)
30
C
LARGE VERTICAL WSHP IM 1059-12
ontrols