Typical Refrigeration Cycles - Daikin Enfinity Installation And Maintenance Manual

Large capacity vertical water source heat pumps
Table of Contents

Advertisement

Typical cooling refrigeration cycle – dual
compressors
Note: Typical temperature readings are at full load con-
ditions at ISO-13256 for boiler-tower applications.
When the wall thermostat calls for COOLING, the
reversing valve (de-energized) directs the flow of the
refrigerant, a hot gas, from the compressor to the water-
to-refrigerant heat exchanger (coaxial heat exchanger).
There, the heat is removed by the water, and the hot
IM 1059-12 LARGE VERTICAL WSHP
gas condenses to become a liquid. The liquid then
flows through a thermal expansion valve to the air-to-
refrigerant heat exchanger coil (evaporator). The liquid
then evaporates and becomes a gas, at the same time
absorbing heat and cooling the air passing over the
surfaces of the coil. The refrigerant then flows as a low
pressure gas through the reversing valve and back to the
suction side of the compressor to complete the cycle.
Figure 39: Cooling refrigeration cycle
50
t
r
yPiCal
efrigeration
www.DaikinApplied.com
C
yCles