Daikin Enfinity Installation And Maintenance Manual page 32

Large capacity vertical water source heat pumps
Table of Contents

Advertisement

Table 13: I/O expansion module terminals locations and
descriptions
H1 – 1
1
I/O Expansion Board Common (Gnd)
H1 – 2
I/O Expansion Board Common (Gnd)
H1 – 3
I/O Expansion Board +5 VDC
H1 – 4
I/O Expansion Board SPI CE1
H1 – 5
I/O Expansion Board SPI CLK
H1 – 6
I/O Expansion Board SPI IN
H1 – 7
I/O Expansion Board SPI OUT
H1 – 8
1
I/O Expansion Board +12 VDC
H1 – 9
I/O Expansion Board 24 VAC
H1 – 10
I/O Expansion Board 24 VAC
H1 – 11
No Connection
H1 – 12
No Connection
H2 – 1
1
Auxiliary Heat / Hydronic Heat Output – N/O
H2 – 2
No Connection
H2 – 3
24 VAC Common
H3 – 1
1
Ext. 24 VAC In
H3 – 2
Ext. 24 VAC Common In
H3 – 3
HGR / Waterside Economizer Output – N/O
H3 – 4
Ext. 24 VAC Common
H3 – 5
Fan Motor – Signal
Figure 20: I/O expansion module terminals locations
www.DaikinApplied.com
H3 – 6
Fan Motor – Common
H4 – 1
1
Entering Water Temp Sensor – Signal
H4 – 2
Entering Water Temp Sensor – Common
H5 – 1
1
No Connection
H5 – 2
No Connection
H5 – 3
Red LED Output
H5 – 4
Green LED Output
H5 – 5
Yellow LED Output
H5 – 6
Red-Green-Yellow LED Common
H6 – 1
HP2-1
Comp #2 High Pressure Switch (HP2) Input Terminal 1
H6 – 2
HP2-2
Comp #2 High Pressure Switch (HP2) Input Terminal 2
H7 – 1
Comp #2 Suction Temp Sensor (LT2) – Signal
H7 – 2
Comp #2 Suction Temp Sensor (LT2) – Common
H7 – 3
Comp #2 Low Pressure Switch (LP2) – Signal
H7 – 4
Auxiliary 24VAC Output
H8 – 1
1
Compressor #2 Output – N/O
H8 – 2
24 VAC Common
H8 – 3
No Connection
H8 – 4
Reversing Valve #2 Output – N/O
H8 – 5
24 VAC Common
TB1 – 1
1
Humidistat (Dehumidification / WSE) Signal Input
TB1 – 2
2
Comp #2 Low Pressure Switch (LP2) – Signal
32
C
LARGE VERTICAL WSHP IM 1059-12
ontrols

Advertisement

Table of Contents
loading

Table of Contents