Daikin EBLQ011CA3V3 Installer's Reference Manual page 88

Hide thumbs Also See for EBLQ011CA3V3:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
A.2.1.8
[7-02]
Number of LWT zones
A.2.1.9
[F-0D]
Pump operation mode
A.2.1.A
[E-04]
Power saving possible
A.2.1.B
User interface location
A.2.1.C
[E-0D]
Glycol present
└─ Options
A.2.2.A
[D-02]
DHW pump
A.2.2.B
[C-08]
External sensor
└────────────────── Control box
A.2.2.E.1
[E-03]
Backup heater steps
A.2.2.E.2
[5-0D]
BUH type
A.2.2.E.3
[D-01]
Preferential kWh rate
A.2.2.E.4
[E-05]
DHW operation
A.2.2.E.5
[C-05]
Contact type main
A.2.2.E.6
[C-06]
Contact type add.
└────────────────── Option box
A.2.2.F.1
[C-02]
Ext. backup heat src
A.2.2.F.2
[C-09]
Alarm output
A.2.2.F.3
[D-08]
External kWh meter 1
A.2.2.F.4
[D-09]
External kWh meter 2
A.2.2.F.5
[C-08]
External sensor
A.2.2.F.6
[D-04]
PCC by digital inputs
└─ Capacities
A.2.3.1
[6-02]
Booster heater
A.2.3.2
[6-03]
BUH: step 1
A.2.3.3
[6-04]
BUH: step 2 (*1)(*2)
└─ Space operation
└─ LWT settings
└────────────────── Main
A.3.1.1.1
LWT setpoint mode
A.3.1.1.2.1
[9-01]
Temperature range
A.3.1.1.2.2
[9-00]
Temperature range
A.3.1.1.2.3
[9-03]
Temperature range
A.3.1.1.2.4
[9-02]
Temperature range
A.3.1.1.5
[8-05]
Modulated LWT
A.3.1.1.7
[9-0B]
Emitter type
└────────────────── Additional
A.3.1.2.1
LWT setpoint mode
A.3.1.2.2.1
[9-05]
Temperature range
A.3.1.2.2.2
[9-06]
Temperature range
A.3.1.2.2.3
[9-07]
Temperature range
A.3.1.2.2.4
[9-08]
Temperature range
└────────────────── Delta T source
A.3.1.3.1
[9-09]
Heating
(*1) *B*CAV3/CAW1_
(*2) *D*CAV3/CAW1_
(*3) *B*CA3*_(*4) *D*CA3*
Minimum temp (heating)
Maximum temp (heating)
Minimum temp (cooling)
Maximum temp (cooling)
Minimum temp (heating)
Maximum temp (heating)
Minimum temp (cooling)
Maximum temp (cooling)
Range, step
Default value
R/W
0: 1 LWT zone
1: 2 LWT zones
R/W
0: Continuous
1: Sample
2: Request
R/O
0~1
0: No
R/W
0: At unit
1: In room
R/W
0: No
1: Yes
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
3: Circul. Pump
4: CP & disinf. Sh
R/W
0: No
1: Outdoor sensor
2: Room sensor
R/W
0: No BUH (*1) (*2)
R/O (*3)(*4)
1: 1 step (*3) (*4)
2: 2 steps
R/W
0~5
R/O (*3)(*4)
1: 1P,(1/1+2)
4: 3PN,(1/2)
5: 3PN,(1/1+2)
R/W
0: No
1: Open tariff
2: Closed tariff
R/W
0: No
1: Yes
R/W
1: Thermo ON/OFF
2: C/H request
R/W
0~2
1: Thermo ON/OFF
R/W
0~3
0
R/W
0: Normally open
1: Normally closed
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: Outdoor sensor
2: Room sensor
R/O
0: No
1: Yes
R/W
0~10kW, step: 0,2kW
3kW
R/W
0~10kW, step: 0,2kW
3kW
R/W
0~10kW, step: 0,2kW
0kW
R/W
0: Fixed
1: Weather dep.
2: Fixed + scheduled
3: WD + scheduled
R/W
15~37°C, step: 1°C
25°C
R/W
37~55°C, step: 1°C
55°C
R/W
5~18°C, step: 1°C
5°C
R/W
18~22°C, step: 1°C
22°C
R/W
0: No
1: Yes
R/W
0: Quick
1: Slow
R/W
0: Fixed
1: Weather dep.
2: Fixed + scheduled
3: WD + scheduled
R/W
15~37°C, step: 1°C
25°C
R/W
37~55°C, step: 1°C
55°C
R/W
5~18°C, step: 1°C
5°C
R/W
18~22°C, step: 1°C
22°C
R/W
3~10°C, step: 1°C
5°C
3/8
Installer setting at variance with
default value
Date
Value
4P522033-1A - 2018.06