Code
[A.2.2.B]
[C-08]
External sensor (outdoor):
When an optional external ambient
sensor is connected, the type of the
sensor must be set. See
guidelines" on
▪ 0 (No)(default): NOT installed. The
thermistor in the user interface and in
the
measurement.
▪ 1 (Outdoor sensor): Remote outdoor
sensor, connected to the outdoor unit.
The outdoor sensor will be used to
measure
temperature.
functionality, the temperature sensor
in the outdoor unit is still used.
▪ 2 (Room sensor): Remote indoor
sensor, connected to option box
EK2CB07CAV3.
sensor in the user interface is NOT
used anymore. Remark: This value
has only meaning in room thermostat
control.
INFORMATION
You can only connect either the remote indoor sensor or
the remote outdoor sensor.
Control box EKCB07CAV3
Modification of these settings is only required when optional control
box EKCB07CAV3 is installed. Control box EKCB07CAV3 has
multiple
functionalities
which
"5 Application guidelines" on
page 12.
#
Code
[A.2.2.E.1]
[E‑03]
▪ 1 (default – read only))
[A.2.2.E.2]
[5-0D]
BUH type:
▪ 1 (default – read only)
Backup heater
[E-03]
configuration
3V3
1
#
Code
[A.2.2.E.4]
[E-05]
DHW operation:
Can the system prepare domestic hot
water?
▪ 0 (No): NOT installed. (Default)
▪ 1 (Yes): Installed
N/A
[E-07]
During domestic hot water preparation,
the heat pump can be assisted by an
electrical heater to ensure the domestic
hot water preparation even for high
desired tank temperatures.
DHW tank type:
▪ 0 (EKHWS): DHW tank with booster
heater installed at the side of the tank.
(Default).
▪ 5 (EKHWP): DHW tank with booster
heater installed at the top of the tank.
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
Description
"5 Application
page 12.
outdoor
unit
are
used
for
the
outdoor
ambient
Remark:
For
some
The
temperature
need
to
be
configured.
See
Description
[5-0D]
1
Description
#
Code
[A.2.2.E.5]
[C-05]
Contact type main
In external room thermostat control, the
contact type of the optional room
thermostat or heat pump convector for
the main leaving water temperature zone
must be set. See
guidelines" on
▪ 1 (Thermo ON/OFF) (default): The
connected external room thermostat or
heat
heating or cooling demand by the
same signal as it is connected to only
1 digital input (preserved for the main
leaving water temperature zone) on
the control box (X2M/1). Select this
value in case of a connection to the
heat pump convector (FWXV).
▪ 2
external
separate heating and cooling demand
and is therefore connected to the 2
digital input (preserved for the main
leaving water temperature zone) on
the control box (X2M/1 and 1a). Select
this value in case of connection with
the wired (EKRTWA) or wireless
(EKRTR1) room thermostat.
If there are two zones (main+additional),
then only Thermo ON/OFF is possible.
[A.2.2.E.6]
[C-06]
Contact type add.
In external room thermostat control with
2 leaving water temperature zones, the
type of the optional room thermostat for
the additional leaving water temperature
zone must be set. See
guidelines" on
▪ 1 (Thermo ON/OFF): See Contact
type main. Connected on the indoor
unit (X2M/1a).
▪ 2: N/A
If there are two zones (main+additional),
then only Thermo ON/OFF is possible.
Option box EK2CB07CAV3
Modification of these settings is only required when option box
EK2CB07CAV3 is installed. Option box EK2CB07CAV3 has multiple
functionalities which need to be configured. See
guidelines" on
page 12.
#
Code
[A.2.2.F.1]
[C-02]
Ext. backup heat src
Indicates if the space heating is also
performed by means of another heat
source than the system.
▪ 0 (default – read only)
8 Configuration
Description
"5 Application
page 12.
pump
convector
sends
(H/C
request):
The
connected
room
thermostat
sends
"5 Application
page 12.
"5  Application
Description
Installer reference guide
the
47