Daikin EBLQ011CA3V3 Installer's Reference Manual page 45

Hide thumbs Also See for EBLQ011CA3V3:
Table of Contents

Advertisement

#
Code
[A.2.1.8]
[7-02]
<< continuation
▪ 1 (2 LWT zones): 2 leaving water
temperature zones. The zone with the
lowest leaving water temperature (in
heating) is called the main leaving
water temperature zone. The zone
with
temperature (in heating) is called the
additional leaving water temperature
zone. In practice, the main leaving
water temperature zone consists of
the higher load heat emitters and a
mixing station is installed to achieve
the desired leaving water temperature.
▪ a: Add LWT zone
▪ b: Main LWT zone
#
Code
[A.2.1.9]
[F-0D]
When the space heating/cooling control
is OFF by the user interface, the pump is
always OFF. When the space heating/
cooling control is On, you can select the
desired pump operation mode (only
applicable during space heating/cooling)
Pump operation mode:
▪ 0 (Continuous): Continuous pump
operation, regardless of thermo ON or
OFF condition. Remark: continuous
pump operation requires more energy
than
operation.
b
b
▪ a: Space heating/cooling control
▪ b: OFF
▪ c: On
▪ d: Pump operation
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
Description
the
highest
leaving
water
a
b
Description
sample
or
request
pump
a
c
c
d
(user interface)
continued >>
#
Code
[A.2.1.9]
[F-0D]
<< continuation
▪ 1 (Sample): The pump is ON when
there is heating or cooling demand as
the leaving water temperature has not
reached the desired temperature yet.
When thermo OFF condition occurs,
the pump runs every 5  minutes to
check the water temperature and
demand
necessary. Remark: Sample is NOT
available in external room thermostat
control or room thermostat control.
a
b
d
g
b
▪ a: Space heating/cooling control
(user interface)
▪ b: OFF
▪ c: On
▪ d: LWT temperature
▪ e: Actual
▪ f: Desired
▪ g: Pump operation
#
Code
[A.2.1.9]
[F-0D]
<< continuation
▪ 2 (Request)(default): Pump operation
based on request. Example: Using a
room thermostat creates thermo ON/
OFF condition. When there is no such
demand, the pump is OFF. Remark:
Request is NOT available in leaving
water temperature control.
a
b
d
e
b
▪ a: Space heating/cooling control
(user interface)
▪ b: OFF
▪ c: On
▪ d: Heating demand (by ext RT or
RT)
▪ e: Pump operation
8 Configuration
Description
heating
or
cooling
if
c
e
f
c
continued >>
Description
c
c
b
c
Installer reference guide
45