14 Technical Data; Service Space: Outdoor Unit - Daikin EBLQ011CA3V3 Installer's Reference Manual

Hide thumbs Also See for EBLQ011CA3V3:
Table of Contents

Advertisement

14
Technical data
A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is
available on the Daikin extranet (authentication required).
14.1

Service space: Outdoor unit

Single unit
e
B
E
e
D
e
H
C
U
b*
c
,†
d
a
D
H
D
A,C
Left side and right side obstacles (walls/baffle plates)
B
Suction side obstacle (wall/baffle plate)
D
Discharge side obstacle (wall/baffle plate)
E
Top side obstacle (roof)
a,b,c,d,e
Minimum service space between the unit and obstacles A, B, C, D and E
*
If shut-off valves are NOT installed on the unit
If shut-off valves are installed on the unit
e
Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle B
B
e
Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle D
D
H
Height of the unit including the installation structure
U
H
,H
Height of obstacles B and D
B
D
H
Height of installation structure below the unit
INFORMATION
If shut-off valves are installed on the unit, provide a
minimum space of 400 mm at the air inlet side. If shut‑off
valves are NOT installed on the unit, provide a minimum
space of 250 mm.
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
A~E
H
B
A, B, C
A, B, C, E
D
D, E
B, D
H
<H
D
B, D, E
H
<H
D
&
B
H
>H
H
B
B
H
>H
D
&
H
<H
B
A
H
H
D
U
a
b*
b
≥500 ≥250
≥400
≥100
≥500 ≥250
≥400
≥150
≥250
≥400
U
≥250
≥400
U
U
≥250
≥400
U
U

14 Technical data

(mm)
c
d
e
e
e
B
D
≥1000
≤500
≥500
≥1000 ≤500
≥500
≥500
≤500
≥1000
≥1000
≥1000 ≥1000 ≤500
*
,†
Installer reference guide
H
≥150
≥150
≥150
≥150
≥150
≥150
≥150
79

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents