Data connection

Connect the sequence data objects defined in the communication structure to the sequence
bay object.
To connect sequence data objects:
1. Right-click the sequence bay and select Data Connection to launch the Data Con-
nection dialog.
Figure 5.2-1 Launching data connection dialog for the bay object
2. In the Data Connection dialog, select Logic_Processor_IED from the IED drop-
down menu.
3. Move all the logical nodes defined for the sequence logical device to the left column
in the dialog using the arrow button, see Figure 5.2-2.
1MRS755001
SAB600_SC_Launch_Data_Connection.png