This section describes the steps involved in configuring a sequence. The same procedure
can be repeated to configure multiple sequences.
Before configuring a sequence, the communication information to multiple IEDs must
be configured. For more information on configuring the communication structure for
COM600, see COM600 User's Manual.
Sequence control views allow you to run configured sequences on COM600. Configuring
sequence control involves the following steps:
defining a sequence logical device and associated logical nodes for the logic processor
IED
defining a sequence (SFC program) in the logic processor
cross-referencing sequence data objects and breaker data objects to corresponding
sequence object and switch object members in the logic processor
defining a sequence SLD for using sequence control through COM600 WebHMI
configuration.
Figure 3.1-1 shows an example of a communication structure in the SAB600 tool
including four IEDs that communicate with COM600 using IEC 61850 protocol.