6. Control Wiring
6.1. Control Terminal Connections
Default Connections
6.2. RJ45 Data Connection
For MODBUS RTU register map information
please refer to page 44
When using MODBUS control the Analog and
Digital Inputs can be configured as shown in
section 9.1.3
Control Terminals
1
+24V
+24V Output
2
DI1
Digital Input 1
3
DI2
Digital Input 2
Digital/Analog
4
DI/AI 3
Input 3
5
+10V
+10V Output
Digital/Analog
6
DI/AI4
Input 4
7
COM
0V
Analog Output /
8
AO
Digital Output
9
AGND
0V
10
ROC
Relay Common
11
RNO
Relay Contact
Description
+24V, 100mA.
Positive logic
"Logic 1" input voltage range: 8V ... 30V DC
"Logic 0" input voltage range: 0V ... 4V DC
Digital: 8 to 30V
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
+10V, 10mA, 1kΩ minimum
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
Digital: 8 to 30V
User ground connected to terminal 9
Analog: 0 to 10V, 20mA maximum
Digital: 0 to 24V
User ground connected to terminal 7
Contact 255Vac, 6A / 30Vdc, 5A
1
2
3
4
5
6
7
8
No Connection
No Connection
0 Volts
-RS485 (PC)
+RS485 (PC)
+24 Volt
-RS485 (Modbus RTU)
+RS485 (Modbus RTU)
Warning:
This is not an Ethernet
connection. Do not connect
directly to an Ethernet port.