Wireless diagnostics
Hide thumbs Also See for FireCell Radio Hub:

Advertisement

Step 5
Is the device allocated to the correct RCC?
RCC2
RCC1
If not try moving the device to the correct/closest RCC. Details can be found within the
FireCell Programming Manual (MK98).
If there is no other RCC to add the device to; an additional RCC may be required, or the
device may require relocation to achieve a better signal.
Step 6
Is the RCC installed as per the survey?
The recommended distance between metal objects from the aerial is 600mm. The
recommended distance to any other electrical equipment is 2 metres.
POWER
FAULT
Step 7
Could anything be blocking the signal?
POWER
FAULT
©2018 EMS Ltd. All rights reserved
Radio Hub
Control Panel
Page 3 of 4
RCC2
RCC1
600mm AWAY FROM
2m AWAY
POWER
FAULT
FROM OTHER
ELECTRICAL
EQUIPMENT
2m AWAY
FROM OTHER
ELECTRICAL
EQUIPMENT
POWER
FAULT
Radio Hub
Control Panel
METAL*
2m AWAY
FROM OTHER
ELECTRICAL
EQUIPMENT
*300mm is an acceptable
distance where 600mm is
not achievable
MK252 Iss 3 15/08/2018