How to resolve a disconnect fault
A device disconnect fault is shown on the Control Panel display, if the communication
path between the individual device and it's associated Radio Cluster Communicator is
not present. The majority of device disconnect faults can be investigated and resolved
by following these 10 simple steps:
Step 1
Is the device in it's location?
Step 2
Is the device powered?
Combined
Sounder
powered by Switch 1 as shown:
www.emsgroup.co.uk
Combined Sounder
and Detector Base
Technical Data see Installation Guide
Part No: FCX-XXX-XXX
0359
Type A: for indoor use
EN54-3: 2001
12
EN54-25: 2008
0359-CPR-00XX
PRESS HERE TO
LOG ON
!
3.5 - 4.5V DC
0.2 - 300mA
1W Max
ON
ON
OFF
1
2
3
4
(Switch 1 On = Power ON)
Step 3
Is the associated RCC powered?
If not, all devices reporting to the RCC will be disconnected.
Disconnected
230Vac
Step 4
Is the ident programmed correctly?
Check the device's ident located on the side of the device under the barcode and cross
reference it with the ident programmed into the Radio Hub.
0C03B
Rev:5 01/08/17
0C03B
Rev:5 01/08/17
©2018 EMS Ltd. All rights reserved
Detectors
are
ON
2
4
1
3
POWER
FAULT
RCC01
RCC01
Page 2 of 4
Other wireless devices have power
jumpers as shown:-
SIZE AA
SIZE AA
SIZE AA
SIZE AA
SIZE AA
(Link pins to power device)
SIZE AA
Connected
230Vac
ID 1C03B
ID 0C03B
MK252 Iss 3 15/08/2018