SETUP
GUIDE
©2024 EMS Ltd. All rights reserved.
MK99 (Issue 9) 23/09/2024 AJM

Advertisement

loading
Need help?

Need help?

Do you have a question about the FireCell and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for EMS FireCell

  • Page 1 SETUP GUIDE ©2024 EMS Ltd. All rights reserved. MK99 (Issue 9) 23/09/2024 AJM...
  • Page 2: Table Of Contents

    6 Assign the Devices 7 Control Panel Programming 8 Check Device Signal Levels 9 Test the System Hub Menu Structure Fault Recti cation How to Improve Signal Levels ©2024 EMS Ltd. All rights reserved. Page 2 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 3: Introduction

    This manual provides a brief step by step guide to setting up the system. Refer to the Programming Manual (MK98), for more comprehensive guidelines. Note: this revision is intended for use with revision 3 software FireCell systems, as previous versions of Hub menu structures will slightly vary. Refer to the legacy version of this document, when using FireCell systems with revision 2 software.
  • Page 4: Install & Log On The Rccs

    If the RCC’s signal path is via another RCC, then the relevant RCC will need to be selected. Each option can be chosen by turning the rotary control. ©2024 EMS Ltd. All rights reserved. Page 4 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 5: Assign The Rccs

    The newly added RCCs should now be assigned. Assign Device Assign RCCs Dev 000 of 001 From Unassigned Dev changing to Done 001 of 001 (once complete) To exit BACK ©2024 EMS Ltd. All rights reserved. Page 5 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 6: Add And Install The Wireless Devices

    The device has now been added to the hub and should be installed in its location, prior to the next step of assigning the device to its relevant RCC. See the relevant devices installation instructions, for more information. ©2024 EMS Ltd. All rights reserved. Page 6 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 7: Assign The Devices

    The newly added devices must now be assigned. Assign Device Assign All Dev 000 of 003 From Unassigned Dev changing to Done 003 of 003 (once complete) To exit BACK ©2024 EMS Ltd. All rights reserved. Page 7 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 8: Control Panel Programming

    Press the ‘Enter’ Button to enter. Con rmation of the addition to the system should now be shown. Once complete, press the ‘Exit’ button to escape the menu. ©2024 EMS Ltd. All rights reserved. Page 8 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 9: Check Device Signal Levels

    Loop 1 address 10 L1 A010 19dB Optical detector Loop 1 address 11 L1 A011 45dB Heat A1R detector Loop 1 address 12 L1 A012 45dB ©2024 EMS Ltd. All rights reserved. Page 9 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 10: Test The System

    The devices automatically come out of fast test mode when the timer expires or the fast test mode is exited. Advanced Start Fast Test Front display To exit BACK ©2024 EMS Ltd. All rights reserved. Page 10 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 11: Hub Menu Structure

    Audio Detect Batt Smoothing Alarm status shown as I/O Status for Input/Output device types. Programming features not yet released in this version of software. † ©2024 EMS Ltd. All rights reserved. Page 11 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 12: Fault Recti Cation

    If so it may need to be moved to an acceptable distance. See hub installation instructions for details. Batteries low Replace all batteries. See the installation instructions for more details on speci ed batteries. ©2024 EMS Ltd. All rights reserved. Page 12 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 13 No action required. Sounder & I/O good/medium Signal strength No action required. good/medium Background No action required. level good Detector Signal strength No action required. medium ©2024 EMS Ltd. All rights reserved. Page 13 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 14 Alarm Check the devices glass is in tact. Detector Alarm Ensure that the environment of the devices location is free of smoke residue and dust. ©2024 EMS Ltd. All rights reserved. Page 14 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 15: How To Improve Signal Levels

    Re-allocate device to correct / closest RCC and re-check signal levels. Carry a survey to re-check signal levels. signal levels now ok? Signal Levels successfully improved. ©2024 EMS Ltd. All rights reserved. Page 15 of 16 MK99 (Issue 9) 23/09/2024 AJM...
  • Page 16 The information contained within this literature is correct at time of publishing. EMS reserves the right to change any information regarding products as part of its continual development enhancing new technology and reliability. EMS advises that any product literature issue numbers are checked with its head o ce prior to any formal speci cation being written.