Installation Guide | VLT® Safety Option MCB 150/151
Shield all proximity switch sensor/encoder cables. Connect the shield to the chassis at both ends. Always connect the chassis
on the rotary encoder to the chassis of the drive.
EQUIPMENT DAMAGE
Plugging in or pulling off sensor connections during operation can damage the electrical components of the encoder.
Always de-energize connected encoders and the safety option before plugging in or pulling off encoder connections.
-
For data signals or track A and track B, use lines twisted in pairs for signal transmission according to RS485.
-
Select the wire cross-section in each individual case in compliance with the current consumption of the encoder and the
-
cable length required for the installation.
Diagnostics are performed on the encoder input signals. If the encoder diagnostic tests fail, error 99 (Safe State Fault) occurs.
4.2.2 Encoder Wiring Examples
See examples of how to connect encoder power and encoder signals in
FC 302
MCB 151
4
A
B
7
10
24 V
GND
11
Illustration 25:
Y31/Connecting Power and Encoder Signals to HTL Encoder (VLT® Safety Option MCB 151)
Danfoss A/S © 2018.09
N O T I C E
N O T I C E
illustration 25
and
illustration
26.
AQ279747441421en-000101 / 130R0292 | 45
Installation