Wiring Configuration Examples; Application Examples; Wiring Configuration For Automatic Motor Adaptation (Ama); Wiring Configuration For Automatic Motor Adaptation (Ama) Without T27 - Danfoss VLT HVAC Drive FC 102 Operating Manual

110-800 kw, d9h-d10h and e5h-e6h enclosed drives
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

VLT® HVAC Drive FC 102
Operating Guide

8 Wiring Configuration Examples

8.1 Application Examples

The examples in this section are intended as a quick reference for common applications.
Parameter settings are the regional default values selected in parameter 0-03 Regional Settings, unless otherwise indicated.
Parameters associated with the terminals and their settings are shown next to the drawings.
Required switch settings for analog terminals A53 or A54 are also shown.

8.1.1 Wiring Configuration for Automatic Motor Adaptation (AMA)

Table 72: Wiring Configuration for AMA with T27 Connected
XD2.10
+24 V
XD2.11
+24 V
XD2.12
D IN
XD2.13
D IN
XD2.18
COM
D IN
XD2.14
D IN
XD2.15
D IN
XD2.16
D IN
XD2.17
D IN
XD2.19

8.1.2 Wiring Configuration for Automatic Motor Adaptation (AMA) without T27

Table 73: Wiring Configuration for AMA without T27 Connected
+24 V
XD2.10
+24 V
XD2.11
XD2.12
D IN
XD2.13
D IN
COM
XD2.18
D IN
XD2.14
D IN
XD2.15
D IN
XD2.16
D IN
XD2.17
D IN
XD2.19
+10 V
XD2.6
A IN
XD2.7
A IN
XD2.8
COM
XD2.9
A OUT
XD2.5
COM
XD2.4
118 | Danfoss A/S © 2021.11
Parameters
Function
Parameter 1-29 Automatic Motor Adaptation (AMA)
Parameter 5-12 Terminal 27 Digital Input
*=Default value
Notes/comments:
Set parameter group 1-2* Motor Data according to motor nameplate.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.
Parameters
Function
Parameter 1-29 Automatic Motor Adaptation (AMA)
Parameter 5-12 Terminal 27 Digital Input
*=Default value
Notes/comments:
Set parameter group 1-2* Motor Data according to motor nameplate.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.
Wiring Configuration Examples
Setting
[1] Enable complete AMA
[2]* Coast inverse
Setting
[1] Enable complete AMA
[0] No operation
AQ262141314214en-000301 / 130R0880

Advertisement

Table of Contents
loading