Installation Guide | VLT® Safety Option MCB 150/151
Message
0 RPM
None
1(1)
Safety Password
Please enter the safety
Password
0
0000000
0 RPM
None
1(1)
Pa
0-
Password accepted
[0
([1] Enabled)
0 RPM
None
1(1)
Pa
0-
Password rejected
[0
([1] Enabled)
0 RPM
0.00A
!1(1)
SO Data Confirmation
Are you sure that you want
to overwrite the safety
parameters including the
level 1 password?
0 RPM
0.00A
!1(1)
SO Data Confirmation
Press [OK] to confirm
(commissioning test must be
performed) or [CANCEL] to
abort
Status
!1(1)
0 RPM
None
0.00KW
SO Custom. completed
SO RESET required!
!Safe Stop [W68]
Off Remote SO Req.RESET
Danfoss A/S © 2018.09
Description
If selecting [VLT:...] and the password protection in parameter 0-69 Password Protection of Safety
Parameters is enabled, enter the correct LCP-copy/parameter mismatch password (parameter 0-68
Safety Parameters Password).
If the entered password is correct, this overlay message is shown for some seconds.
If the entered password is wrong, this overlay message is shown for some seconds. Then the pass-
word can be entered again.
Decision box for continuing overwriting the existing data or to abort the procedure.
Press [OK] to complete the customization of the safety option. A reset is required to finalize this
procedure.
Service and Repair
AQ279747441421en-000101 / 130R0292 | 73