8.4 List of Warnings and Alarms

An (X) marked in Table 8.1 indicates that the warning or alarm has occurred.
No.
Description
2
Live zero error
3
No motor
4
Mains phase loss1)
7
DC overvoltage
8
DC undervoltage
9
Inverter overloaded
10
Motor ETR overtemperature
8
8
Motor thermistor overtem-
11
perature
12
Torque limit
13
Overcurrent
14
Ground fault
16
Short circuit
17
Control word timeout
25
Brake resistor short-circuited
26
Brake overload
Brake IGBT/Brake chopper short
27
circuited
28
Brake check
30
U phase loss
31
V phase loss
32
W phase loss
34
Fieldbus fault
35
Option fault
36
Mains failure
38
Internal fault
40
Overload T27
44
®
VLT
Midi Drive FC 280
Warning
X
X
X
1)
X
1)
X
X
X
X
X
X
X
X
X
X
X
X
Danfoss A/S © 11/2015 All rights reserved.
Alarm
Trip lock
Cause
Signal on terminal 53 or 54 is less than 50% of value set
in parameter 6-10 Terminal 53 Low Voltage,
X
parameter 6-20 Terminal 54 Low Voltage and
parameter 6-22 Terminal 54 Low Current.
No motor has been connected to the output of the
adjustable frequency drive.
Missing phase on supply side, or the voltage imbalance is
X
X
too high. Check the supply voltage.
X
DC link voltage exceeds limit.
DC link voltage drops below the voltage warning low
X
limit.
X
More than 100% load for too long.
Motor is too hot due to more than 100% load for too
X
long.
Thermistor or thermistor connection is disconnected, or
X
the motor is too hot.
Torque exceeds value set in either parameter 4-16 Torque
X
Limit Motor Mode or parameter 4-17 Torque Limit Generator
Mode.
Inverter peak current limit is exceeded. If this alarm
X
X
occurs on power-up, check whether power cables are
mistakenly connected to the motor terminals.
X
X
Discharge from output phases to ground.
X
X
Short circuit in motor or on motor terminals.
X
No communication to the adjustable frequency drive.
Brake resistor is short circuited, thus the brake function is
X
X
disconnected.
The power transmitted to the brake resistor over the last
X
120 s exceeds the limit. Possible corrections: Decrease
brake energy via lower speed or longer ramp time.
Brake transistor is short-circuited, thus the brake function
X
X
is disconnected.
X
Brake resistor is not connected/working.
X
X
Motor phase U is missing. Check the phase.
X
X
Motor phase V is missing. Check the phase.
X
X
Motor phase W is missing. Check the phase.
X
PROFIBUS communication issues have occurred.
X
Serial communication bus detects internal errors.
This warning/alarm is only active if the supply voltage to
the adjustable frequency drive is less than the value set
X
in parameter 14-11 Mains Voltage at Mains Fault, and
parameter 14-10 Mains Failure is NOT set to [0] No
Function.
X
X
Contact the local Danfoss supplier.
Check the load connected to terminal 27 or remove short
circuit connection.
MG07A122