Programming
5.2 Main menu
The following menu items are available to you in the main menu:
•
Meter setup
•
Measuring
•
Inputs and outputs
•
Reset of the totalizer
•
Setting of communication port
•
Specific counter settings
•
Counter information
•
Language selection
5.2.1 Meter setup
Scale Factor
Empty Pipe
Detection
Power Line
Frequency
Excitation
Frequency
You may chose this factor to optimize an accuracy or to achieve an
accuracy in flow measurement that is close or better than the
reproduceability of the meter. This factor corrects the actual flow rate in
percent (positively or negatively).
Note: Changing this value has an influence on the meter accuracy!
Fluid monitoring shows if measuring pipe has only partly been
with liquid. Monitoring can be switched on or off.
Note: On request, fluid monitoring can be adjusted to fluid's conductivity
or to cable length.
For an optimum operation of the meter, set Power Line Frequency in
this menu at operating location.
This value shows in which frequency the meter's coils are operated.
Supported frequencies are dependent on the configured power line
frequency and meter's size.
Note: When selecting excitation frequency, make sure to always
observe that the ratio in respect of power frequency is integer.
MID_M2000_BA_02_1807
50 Hz
60 Hz
1 Hz
1 Hz
3.125 Hz
3.75 Hz
6.25 Hz
7.5 Hz
12.5 Hz
15 Hz
Page 17/51
filled